Appendix A.13.  DnpSubType 
DNP objects often contain more than one element of information, e.g. Object 30, variation 1 is a 32-
bit  analog  input.    When  the  DNP  device  is  polled  for  data  for  this  object  the  device  returns  a  data 
structure  which  contains  a  32  bit  value  for  the  input  and  an  8  bit  status  byte  indicating  the  input’s 
quality.  Alternatively the FieldServer defaults to the value subtype. 
 
By  using  the  value  or  flags  in  the  field  for  dnpSubType  you  could  have  the  FieldServer  extract  the 
value or the status byte and place them in the data array associated with the Map Descriptor.  In this 
example it  would have made no sense to try  and extract a time as there is no time field associated 
with object 30, variation 1. 
 
Permitted Values 
Description 
Value 
The driver extracts the value of the object being read. 
Flags 
The driver extracts the quality/status byte of the object. 
Time1 
The driver extracts the time field from the object. 
Time2 
The driver extracts a second time field from the object if the object has more 
than one. 
Combo 
 
(NB  -  only  valid  with 
Object  12,  Variation 
1;  
Object  41,  Variation 
1 & 2) 
Used  with  a  write  Map  Descriptor  with  the  dnpFunction  set  to  5  (Direct 
Operation with no Ack).  The driver uses multiple consecutive elements from 
the data array to build the write command. 
 
When used with Object 12 Variation 1. 
The 1
st
 array element is used as a byte to fill in the control code field. 
The 2
nd
 array element is used as a byte to fill in the count field. 
The 3
rd
 array element is used as a UINT32 to fill in the on time field. 
The 4
th
 array element is used as a UINT32 to fill in the off time field. 
The status field is always set to zero. 
 
When used with Object 41 Variation 1 & 2 
The 1
st
 array element is used as a INT32 (variation 1) or INT16 (variation2) 
to fill in the requested value  field. 
The 2
nd
 Array Element is used as a byte to fill in the control status field. (See 
the definition of object 12 for a description of this field.) 
 
Appendix A.14.  Communication Stats 
The  driver  counts  bytes  on  the  connection  and  messages  on  the  Map  Descriptors.    Thus  if  a  Map 
Descriptor is used to generate a poll then the transmit messages increment and when a response is 
received, its received messages will increase.  The byte count of these messages will be counted on 
the connection and not on the Map Descriptor.  The connection also counts messages and bytes that 
form connection related messages such as link resets, confirms, acks, naks…. 
Appendix A.15.  Link Reset 
The  Link  Reset  message  forms  part  of  the  Data  Link  layer  of  the  DNP  3.0  protocol.    It  is  used  to 
establish and check a connection.  When configured  as a Client, the driver sends a Link Reset and 
waits for the Server to respond before starting data transfer.  When configured as a Server, the driver 
will not respond to messages until the remote Client  has sent a Link Reset.  The following example 
configuration will override this default behavior. 
 
Example 
 
//    Server Side Connections 
 
 
 
 
 
Connections 
 
 
 
 
Port 
,Baud 
,Parity 
,Protocol 
,Application 
P8 
,9600 
,None 
,DNP 
,NoLink