FieldServer FS-8700-47 Manuale Utente

Pagina di 51
FS-8700-47 DNP 3.0 Driver Manual 
 
 
 
 
 
 
Page 7 of 51 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
3. 
Hardware Connections 
The FieldServer is connected to the DNP-3.0 device as shown below. 
Configure the DNP-3.0 device according to manufacturer’s instructions 
 
8917-04
DB25F
FieldServer
RJ45
Connect to one of the RS-232 
Ports on the FieldServer
P1
1
8
DNP Device
 
 
 
 
FieldServer Function  From 
Default 
Color 
Rx 
RJ45-01  DB25F-02  White 
CTS 
RJ45-02  DB25F-04  Brown 
DSR 
RJ45-03   
Yellow 
GND 
RJ45-04  DB25F-07  Green 
GND 
RJ45-05   
Red 
DTR 
RJ45-06   
Black 
RTS 
RJ45-07  DB25F-05  Orange 
Tx 
RJ45-08  DB25F-03  Blue 
 
3.1. 
Connection Notes 
Pinouts and adapters may vary according to the device being connected to.  Refer to DNP installation 
manual for pin connection reference.