FieldServer FS-8700-80 Manuale Utente

Pagina di 35
McQuay Micro Tech Open Protocol Driver Manual 
 
 
 
Page 3 of 35 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldServer.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldServer.com 
1. 
McQuay Micro Tech Open Protocol Description  
This  document  describes  the  FieldServer  driver  used  to  transfer  data  between  a  FieldServer  and 
MicroTech®  controllers.    Transfers  are  done  using  the  controller's  Data  Terminal  Communications 
Protocol.  In this document the protocol is referred to as the McQuay Micro Tech Open Protocol. 
 
The McQuay Micro Tech Open Protocol driver allows the FieldServer to transfer data to and from devices 
over  either  RS-232  or  RS-485  using  McQuay  Micro  Tech  Open  Protocol.  The  FieldServer  can  emulate 
either a Server or Client.  
 
When  emulating  a  Client,  the  driver  enables  the  FieldServer  to  request  ‘Everything’  from  the  McQuay 
device  as  well  as  a  number  of  advanced  options  which  allow  specific  fields  to  be  read  or  written  and 
device scaling to be applied. 
 
When emulating a Server, the driver provides an emulation of the byte memory of a device and responds 
to read and write requests. 
 
The following important points and limitations should be noted before proceeding with this manual. 
 
1.  Arising from a feature of the McQuay Micro Tech Open Protocol is the peculiarity, that when a multi-
byte value is written to a McQuay device, the write is done one byte at a time (one byte of data can 
be transferred per poll/response message pair) allowing for the possibility (at least for a short period) 
that the multi byte value is only partially correct until all the messages have been completed. 
2.  The vendor equipment is limited to a maximum of 9600 baud. Given that each message packet can 
only  transfer  one  byte  of  data  and  that  some  data  of  interest  is  multi-byte,  users  of  this  protocol 
should expect low data transfer rates. 
3.  Port expansion is not supported for this driver. 
4.  A  document  identified  as  Ed15050  MicroTech  Network  Operations  contains  important  information 
regarding the connection requirements of 3rd party equipment such as the FieldServer to a Microtech 
network.    The  document  also  defines  a  number  of  limitations  for  such  connections.    The  following 
quotations from this document outline some of this information.