W7 ASD Installation and Operation Manual
5
Installation Precautions
Location and Ambient Requirements
The Toshiba ASD is intended for permanent installations only.
Installation should conform to the 2005 National Electrical Code — Article 110 (Requirements 
For Electrical Installations
), all regulations of the Occupational Safety and Health 
Administration
, and any other applicable national, regional, or industry codes and standards.
Select a mounting location that is easily accessible, has adequate personnel working space, and 
adequate illumination for adjustment, inspection, and maintenance of the equipment (refer to 2005 
NEC Article 110-13).
A noncombustible insulating floor or mat should be provided in the area immediately surrounding 
the electrical system.
Do Not mount the ASD in a location that would produce catastrophic results if it were to fall from 
its mounting location (equipment damage or injury).
Do Not mount the ASD in a location that would allow it to be exposed to flammable chemicals or 
gasses, water, solvents, or other fluids.
Avoid installation in areas where vibration, heat, humidity, dust, fibers, metal particles, explosive/
corrosive mists or gases, or sources of electrical noise are present.
The installation location shall not be exposed to direct sunlight.
Allow proper clearance spaces for installation. Do not obstruct the ventilation openings. Refer to 
the section titled 
 for further information on ventilation 
requirements.
The ambient operating temperature range of the W7 ASD is 14 to 104° F (-10 to 40° C).
See the section titled 
 for additional information on installing 
the drive.
Mounting Requirements
Only 
 should install this equipment.
Install the unit in a secure and upright position in a well-ventilated area.
A noncombustible insulating floor or mat should be provided in the area immediately surrounding 
the electrical system at the place where maintenance operations are to be performed.
As a minimum, the installation of the equipment should conform to the 2005 NEC Article 110 
Requirements For Electrical Installations, OSHA, as well as any other applicable national, regional, 
or industry codes and standards.
Installation practices should conform to the latest revision of NFPA 70E Electrical Safety 
Requirements for Employee Workplaces.
It is the responsibility of the person installing the ASD or the electrical maintenance personnel to 
ensure that the unit is installed into an enclosure that will protect personnel against electric shock.