52
W7 ASD Installation and Operation Manual
Acceleration Time #1
Program 
 
Fundamental Parameters 
 
Fundamental #1 
 
Accel 
Time #1
This parameter specifies the programmed time in seconds for the output of the 
ASD to go from 0.0 Hz to the Maximum Frequency for the #1 Acceleration 
profile. The accel/decel pattern may be set using Accel/Decel #1 Pattern. The 
minimum and maximum accel/decel time may be set using S-Pattern Lower 
Limit Adjustment
 and the S-Pattern Upper Limit Adjustment.
Note: An acceleration time shorter than the load will allow may 
cause nuisance tripping and mechanical stress to loads.
 
 
Automatic Accel/Decel and Stall settings may lengthen the 
acceleration time.
Acceleration
The acceleration rate of a motor is determined by several factors: applied 
power, applied load, and the physical properties of the motor (winding 
parameters, motor size, etc.). The ASD will control the first of these factors: 
input power. The settings of the ASD control the frequency and amplitude of 
the applied voltage to the motor.
Under most operating conditions, as the output frequency of the ASD goes up 
so does the output voltage (linear acceleration). The ASD has the ability to 
modify the relationship between frequency and voltage automatically to 
produce smoother operation or increased (starting) torque.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Accel #2 Time
Program 
 
Fundamental Parameters 
 
Fundamental #2 
 
Accel 
Time #2
This parameter specifies the programmed time in seconds for the output of the 
ASD to go from 0.0 Hz to the Maximum Frequency for the #2 Acceleration 
profile. The accel/decel pattern may be set using Accel/Decel #2 Pattern. The 
minimum and maximum accel/decel time may be set using S-Pattern Lower 
Limit Adjustment
 and the S-Pattern Upper Limit Adjustment.
This setting is also used to determine the acceleration rate of the Motorized Pot 
function.
Note: An acceleration time shorter than the load will allow may 
cause nuisance tripping and mechanical stress to loads.
 
Automatic Accel/Decel and Stall settings may lengthen the 
acceleration time.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds