Basic Installation 3-3
MN1942
3.2 Mechanical installation and cooling requirements
It is essential that you read and understand this section before beginning the
installation
.
CAUTION: To prevent equipment damage, be certain that the input power has correctly
rated protective devices installed.
CAUTION: To prevent equipment damage, be certain that input and output signals are
powered and referenced correctly.
CAUTION: To ensure reliable performance of this equipment be certain that all signals
to/from the MicroFlex e100 are shielded correctly.
CAUTION: Avoid locating the MicroFlex e100 immediately above or beside heat
generating equipment, or directly below water steam pipes.
CAUTION: Avoid locating the MicroFlex e100 in the vicinity of corrosive substances or
vapors, metal particles and dust.
CAUTION: Failure to meet cooling air flow requirements will result in reduced product
lifetime and/or drive overtemperature trips.
The safe operation of this equipment depends upon its use in the appropriate environment.
The following points must be considered:
H
The MicroFlex e100 must be installed indoors, permanently fixed and located so that it can
only be accessed by service personnel using tools.
H
The maximum suggested operating altitude is 1000m (3300ft).
H
The MicroFlex e100 must be installed where the pollution degree according to IEC664 shall
not exceed 2.
H
The 24VDC control circuit supply must be installed so that the 24VDC supplied to the unit is
isolated from the AC supply using double or reinforced insulation.
H
The input of the control circuit must be limited to Safety Extra Low Voltage circuits.
H
Both the AC supply and the 24VDC supply must be fused.
H
The atmosphere must not contain flammable gases or vapors.
H
There must not be abnormal levels of nuclear radiation or X-rays.
H
To comply with CE directive 89/336/EEC an appropriate AC filter must be installed.
H
The MicroFlex e100 must be secured by the slots in the flange. The protective earth/ground
(the threaded hole on the top of the MicroFlex e100) must be bonded to a safety earth/ground
using either a 25A conductor or a conductor of three times the peak current rating -
whichever is the greater.
H
The threaded holes in the top and bottom of the case are for cable clamps. The holes are
threaded for M4 bolts no longer than 11mm (0.43 in) in length.
H
The D-type connectors on the front panel of the MicroFlex e100 are secured using two
hexagonal jack screws (sometimes known as “screwlocks”). If a jack screw is removed
accidentally or lost it must be replaced with a #4-40 UNC jack screw with an external male
threaded section no longer than 10mm (0.4 in).