Variables
GFK-1918D
CIMPLICITY Logic Developer - PLC Version 4.00
17
To  cr eat e a  va ri ab le
1.
In the 
 Variables tab of the  
Navigator, right-click  
 Variable List, point to New Variable and then 
choose the data type of the variable.
The New Variable dialog box appears.
2.
Type a name for the variable and press 
ENTER
.
Variable names can range from 1 to 32 characters, begin with a letter, contain 
upper or lower case letters, use numbers between zero and nine, and use the 
underscore character (“_”).
3.
Select the target the variable will be used in.
4.
If the new variable is an array, select the Array check box and enter the size(s).
5.
Click OK.
A new variable with a default name appears in the list.
To  ma p  a v ar iab le t o  PL C m emo ry  
In order to successfully download a project to the PLC, variables must be properly 
mapped to the PLC’s memory, unless they are symbolic variables, which a 
PACSystems™ RX7i will automatically map for you. There are two ways to map a 
non-symbolic variable.
First method:
1.
In the 
Variables tab of the 
Navigator, right-click a variable and choose Properties
The Inspector displays the properties of the variable. 
2.
In the Ref Address field, enter an address. You can:
Spell out the exact address, for example, %R00123 or 123R. In either case this 
maps the variable to %R00123.
Enter only the memory area, for example %R. This maps the variable to the next 
highest available address. For example, if %R00122 was the last address used, 
entering %R maps the variable to %R00123.
New Variable menu