Omega DPF76 Manuale Utente

Pagina di 30
5
WHAT CAN YOU VIEW?
1) "A sub B" - If you have selected the "A sub B" mode, pressing "view" shows:
A) The net result of subtracting input B from input A. Pulses on input B will subtract (count down).  Pulses on input A
will add (count up) if "reset to 0" is selected, if "set to preset" is selected, input A will subtract (count down).
B)  The rate of input A.
2)  "A add B" - If you have selected "A add B" mode,  pressing "view" shows:
A)  The net result of adding "A" and "B" inputs. Pulses on input B will add (count up).  Pulses on input A will add
(count up) if "reset to 0" is selected, if "set to preset" is selected input A will subtract (count down).
B) The rate of input A.
3)  "A sep B" - If you have selected " A sep B" mode, pressing "view" shows:
A) The total counts of input A.  If "reset to 0" is selected A counts up, if "set to preset" is selected A will count down.
B) The rate of input A.
C)* The total counts of input B.  B will always count up.
NOTE:  In "A sep B" mode, B can be used in 3 ways:
1) As a separate totalizing counter
2)** As a Batch Total Counter for input A
3)** As a Grand Total Counter for input A
NOTE:
  * All decimal points are inverted when "B total" is being displayed.
** See below on how to modify for Batch Count and "B" as a Grand Total Counter.
MILLIVOLT INPUT OPTION
JUMPER SELECTIONS
OUTPUT JUMPER SELECTIONS
FUNCTION
"A" RELAY
N.C. OUTPUT
"B" RELAY
N.C. OUTPUT
"A" PRESET
TRANSISTOR (NPN)
"B" PRESET
TRANSISTOR (NPN)
"B" AS BATCH
COUNTER
"B" AS GRAND
TOTAL COUNTER
MODIFICATION
CUT            JUMPER
AT "A"       "B" TO "2"
CUT            JUMPER
AT "D"       "E" TO "4"
CUT            JUMPER
AT "A"       "C" TO "2"
CUT            JUMPER
AT "D"       "F" TO "4"
SELECT     JUMPER
"A SEP B"   "H" TO "G"
SELECT      CONNECT
"A SEP B"    PULSES TO
                      "A" & "B"
BOTTOM VIEW  AT TERMINAL
D
E
G
H
20192
12  11  10   9    8    7    6    5    4    3    2    1
L
4
A
B
2
F
C
J4
J5
J6
J3
J1
J2
CR1
R3
C8
R7
R5
R4
U1
CR2
REV
20229
CR6
CR3
U3
P1
R10
R6
C6
C7
CR4
CR5
C4
R2
R1
C3
C5
U2
U4
U6
U5
R8
R9
C1
C2
C9
B
If the unit has the millivolt input bd.# 20229, A & B inputs can be
separately solder jumper programmed to accept either a low milli-
volt or 4-30 V input.  Each unit shipped is programmed according
to part number.  If solder jumpers are made, the part number
should be modified to reflect the changes made
C=CLOSE, O=OPEN
4-30V INPUT
Millivolt INPUT
Input A
J1-O, J2-C, J3-O
J1-C, J2-O, J3-C
InputB
J4-O, J5-C, J6-O
J4-C, J5-O, J6-C
*
*
* The unit must be removed from the case to access jumpers C & F, all
other jumpers can be accessed by removing the plastic extender.
NOTE: All three pads at jumpers 2 and 4 are connected.