Installation and Quick Start
Installation in a UPS
Overview
You can install the Management Card in a card slot in a 
Smart-UPS, Matrix-UPS, or Symmetra. For a Silcon UPS, the 
Management Card installs in a Silcon Triple Expansion 
Chassis (AP9604S).
Step 1: Turn off 
all power 
(Smart-UPS or 
Matrix-UPS)
You do not need to turn power off for a Symmetra UPS.
Smart-UPS
1. Turn off the 
equipment that 
connects to the 
UPS.
2. Disconnect the 
UPS from its AC 
input source.
3. Press the OFF 
button on the 
UPS for 
approximately 
five seconds to 
turn off the DC 
(battery) power.
Matrix-UPS
1. Turn off the 
equipment that 
connects to the 
UPS.
2. Turn off the 
circuit breaker on 
the rear panel of 
the UPS.
Caution
Damage to the 
UPS
 or Management Card can 
result if you do not remove all 
AC
 and 
DC
 power 
from a Smart-UPS or Matrix-UPS model UPS. 