AS-Interface Slaves
AS-Interface motor starters and IP20 load feeders
AS-Interface load feeder modules IP20
6
Overview
 
AS-Interface load feeder module 
The AS-Interface load feeder module serves as an additional in-
put/output module for the conventional busbar and standard 
mounting rail adapters. It enables the control circuit of a load 
feeder to be completely prewired. The series has been opti-
mized for use in conjunction with the SIRIUS load feeders (sizes 
S00 and S0). The connection to the higher-level automation sys-
tem is made via the interface between the AS-Interface and the 
load feeder module. An unshielded, standard litz wire can be 
used as the data line and for the 24 V DC load power supply. The 
connection to the AS-Interface load feeder module is made by 
means of two insulation-piercing connectors.
Four different AS-Interface load feeder modules are available: 
The versions differ in the number of inputs and outputs, as well 
as in the type of outputs. The units with electronic outputs are de-
signed for 24 V 
DC
, whereas units with relay outputs are de-
signed for voltages of up to 230 V AC. They enable direct-on-line 
and reversing starters, double direct-on-line starters and starter 
combinations to be wired for pole-changing. The status signals 
from the circuit-breakers and the contactor(s) can be interro-
gated separately at the inputs. The outputs are used to control 
the contactor coils directly.
Since the outputs already have overvoltage protection inte-
grated, additional measures are not required for the contactors.
The outputs are fed by a separate auxiliary power supply, which 
facilitates a selective emergency stop concept. The inputs are 
supplied via the AS-Interface data line. The inputs and outputs 
must be wired via integrated Cage Clamp terminals which are 
connected to a common potential. 
3RA5 fuseless load feeder with connection to an 
AS-Interface 
The 3RA5 fuseless load feeder, consisting of AS-Interface load 
feeder module, circuit-breaker and contactor, together with all 
necessary connectors (AS-Interface, auxiliary power and 5-pole 
power connector), is supplied completely assembled, wired and 
tested. This saves the user valuable time required for installation, 
wiring and servicing. 
Also available are direct online starters and reversing starters 
with SIRIUS switchgear of sizes S00 up to 10 A and size S0 - de-
termined by the power connector - for up to 16 A. The complete 
feeder units are available with AS-Interface load feeder modules 
with electronic outputs for an auxiliary voltage of DC 24 V.
Load feeder units of this kind are used, for instance, to control 
standard three-phase motors. The load feeders can be installed 
in central switchgear cubicles or in distributed, onsite switch-
gear boxes. They are particularly suitable for machines and 
plants where the degree of automation is high and special im-
portance is attached to availability.
Design
The AS-Interface load feeder module is snapped onto a match-
ing support for switching devices. A 5-pole power supply con-
nector can optionally be fitted between the load feeder module 
and the support. 
If this connector is used, all the load feeder connections are of 
the plug-in type. The unit can thus be replaced very easily if nec-
essary. If this connector is used, the current is limited to 16A.
Several versions of the controlgear support are available; the 
choice depends on the width of the controlgear combination 
(45 mm or 54 mm) and on the busbar system which is used (bus-
bar center-line spacing 40 mm or 60 mm). Depending on the 
variant, the N and/or PE conductors or neither conductor is 
brought out as well. The connecting cables of the loads can thus 
be prefabricated beforehand and laid directly to the AS-Inter-
face load feeder module via the optional power supply connec-
tor, then installed at this module without any additional wiring. 
The loads, for example a three-phase standard motor, can be 
exchanged easily in this way.
Each AS-Interface bus station must be assigned a unique ad-
dress at the commissioning stage at the latest. In the case of the 
AS-Interface load feeder module, this can be achieved either via 
the master by plugging in the connectors which are connected 
to the data line one at a time (only one station in the network is 
allowed to respond to the default address 0), or by allocating in-
dividual addresses by means of the addressing device and line. 
This addressing method can still be used even if the compact 
starter is fully wired, as the module is disconnected from the 
AS-Interface network as soon as the addressing connector is 
inserted.
The addressing socket is located underneath the item code 
plate on the front of the load feeder module. The LEDs for diag-
nosing the AS-Interface load feeder module are also situated 
there. The following states are displayed:
• 24 V DC auxiliary voltage present or output/outputs set 
(230 V AC version)
• AS-Interface communication o.k.
• AS-Interface communication fault
• Station address = 0 (module not addressed)