Siemens EN 50295 Manuale Utente

Pagina di 152
Siemens IK PI · 2004
6/141
AS-Interface Power Supply Units
Power supply units IP65
6
Technical specifications
 
1) The counterpart is not included in the scope of supply (see accessories).
AS-Interface IP65 power supply unit 
Rated input voltage 230 V AC 
Rated input voltage 24 V DC 
3RX9 311-0AA00 
6EP1 632-1AL01 
Output current in A
2.4
2.4
Rated input voltage in V
230 AC
24 DC
Input
• Rated input voltage U
e rated
 in V
230 AC
24 DC
• Range selection
Changeover contact (internal)
--
• Input voltage range in V
195 to 253
20.4 to 28.8 DC
• Overvoltage resistance
EN 61 000-4-1
35 V DC for max. 500 ms
• Mains buffering at I
e rated 
in ms
> 20
> 10
• Mains frequency rated value I range  
in Hz
50/60/47 to 63
--
• Input current rating I
e
 
rated
 in A
< 0.5
3.6
• Built-in input fuse in A
T 2 (not accessible)
T 6.3 (not accessible)
Output
• Stabilized floating DC voltage 
acc. to AS-Interface specification
Yes
Yes
• Rated output voltage U
a rated
 in V
30 DC (AS-Interface)
30 DC (AS-Interface)
• Total tolerance
29.5 to 31.6 V DC
29.5 to 31.6 V DC
• Residual ripple in mVpp
< 300
< 300
• Spikes in mVpp
< 50
< 50
• Operational display
Green LED
Green LED
• Output current rating I
a rated 
in A
2.4 (power boost 2.8)
2.4
Efficiency/power loss
• Efficiency at U
a rated
I
a rated
 in %
Approx. 85
> 81
• Power loss at U
a rated
I
a rated
 in W
Approx. 10
< 17
Protection and monitoring functions
• Output overvoltage protection
No
--
• Current limitation in A
> 2.8
From approx. 2.9
• Short-circuit protection
Yes
Stabilized current approx. 2.9 A
Safety
• Primary/secondary isolation
Yes (SELV to EN 60 950)
Yes (SELV to EN 60 950)
• Safety class
Class I to IEC 536
Class I to IEC 536
• Degree of protection
IP65
IP65
• Approvals
CE, UL, CSA (in preparation)
CE, UL, ship building
EMC
• Emitted interference
EN 50 081-1
EN 50 081-1, EN 55 022 Cl. B
• Noise immunity
EN 50 082-2
EN 50 082-2
Operational data
• Ambient temperature range in °C
-45 to +55
-25 to +55
• Transport and storage 
temperature range in °C
-45 to +60
-25 to +85
• Humidity class
Max. 80% rel. humidity
F to DIN 40 040
Mechanical data
• Input connection
Amphenol device socket
Circular connector 0.5 to 2.5 mm
21
)
• Output connection AS-i +
AS-i+/AS-i: via yellow AS-Interface cable
500 mm 3-wire conductor AWG 14
• Output connection AS-i -
FK line adapter
500 mm 3-wire conductor AWG 14
• Output connection Ground
--
500 mm 3-wire conductor AWG 14
• Dimensions (W x H x D) in mm
105 
´ 155 ´ 117
224 
´ 80 ´ 57
• Mounting
Mounting onto standard rails
DIN EN 50 022-35 x 7.5
Wall mounting
Special function
--
--
Accessories
--
6-pole connector for input voltage (6ES5 760-2CA11) 
and AS-Interface coupling module PG 
(3RG9 220-0AA00) must be ordered separately