AS-Interface Slaves
I/O modules for operation in the field
Digital I/O modules IP68 / IP69K - K60R
6
Overview
 
Modules with the degree of protection IP67 cannot be used in 
environments with permanently high humidity, with drilling emul-
sions and cutting oils or for cleaning with high-pressure clean-
ers. For these applications, the extension for the K60 compact 
modules, the K60R module with degree of protection IP68 / 
IP69K, is the solution.
The K60R modules are connected via a round cable with a M12 
cable plug instead of the AS-Interface ribbon cable. 
The AS-Interface bus cable and 24 V DC auxiliary power are 
routed in a common round cable.
The degree of protection IP68 permits many new areas of appli-
cations for which the previous field modules with degree of pro-
tection IP67 could not be used. The K60R with degree of protec-
tion IP68 makes it possible to use the module for applications 
such as bottling plants or machine tools on-site in areas sub-
jected to permanently high humidity. This allows the savings in 
wiring outlay due to AS-Interface to be implemented with even 
greater consistency. For IP68 test conditions see Section 
Tests IP68 / IP69K.
Cleaning with pressurized cleaning equipment, as is frequently 
necessary in the food, beverages and tobacco industries, is 
problem-free (IP69K).
When trailing cables are used, many users require that the AS-
Interface bus cable is routed in a round cable. The K60R module 
permits direct connection to a round cable. An adapter is not re-
quired.
Design
Mounting
The same mounting plates are used as for the K60 modules. 
The K60R is connected using a 4-conductor round cable with an 
M12 connection instead of using ribbon cables. The mounting 
plate therefore only serves for the K60R as a mounting point and 
grounding connection. 
Addressing
Addressing is carried out using the same socket as for the bus 
connection. The connection of the module to the addressing unit 
3RK1 904-2AB01 is carried out with a standard M12 cable 
(e.g. 3RX1 642). A special addressing line (3RK1901-3RA00) is 
required when using the older version of the addressing unit 
3RK1 904-2AB00. Following mounting, the module is connected 
to the addressing unit using the addressing line, and then 
addressed. The addressing line is subsequently removed, and 
the module connected to the bus cable.
NSA0_00338
Socket for bus connection and addressing