Siemens EN 50295 Manuale Utente

Pagina di 152
Siemens IK PI · 2004
6/9
AS-Interface
AS-Interface Safety at work
AS-Interface safety monitors
6
Overview
The safety monitor is the core component of Safety at Work. A 
safe application is configured with a PC via the safety monitor. 
Various different application-specific operating modes can be 
used. These include the EMERGENCY-STOP function, tumbler, 
two-handed operation as well as selection of Stop category 
0 or 1.
In order to fully utilize the AS-Interface diagnostic capability, the 
monitor can also be operated with AS-Interface addresses as an 
alternative.
Two versions of the monitor are available:
• Safety monitor with one two-channel release circuit
• Safety monitor with two two-channel release circuits
Function
Safety monitor with enlarged functions
Logical OR operation 
In this logical operation up to six elements can be OR gated. 
(Until now, only two elements could be OR gated). 
Logical AND operation 
In addition to the standard AND gating in the main path of an 
enabling circuit, an AND operation can be inserted into an OR 
operation. More than two elements can be gated in this AND.
Buffer 
Temporary shutdowns are stored in a buffer for the purpose of 
diagnostics.
Number of devices 
The number of devices that the safety monitor can process has 
been increased from 32 to 48. Applications that are larger and 
more complex can now be simulated in the safety monitor.
Timer functions 
Timers are offered with the functions
• Delayed switching-on 
• Delayed switching-off and
• Pulse.
Compatibility 
Any configurations that have been previously created can be 
loaded into the "new" safety monitor without changes.
Technical specifications
 
Safety monitor 
3RK1 105
Rated operational current 
• I
e
/AC-12
up to 250 V, 2 A
• I
e
/AC-15
115 V, 2A 
230 V, 2A
• I
e
/DC-12
up to 24 V, 3 A
• I
e
/DC-13
24 V, 1 A 
115 V, 0.1 A 
230 V, 0.05 A
• Response time
< 40 ms
• Ambient temperature in °C
0 to +60
• Storage temperature in °C
-40 to +85