Network  
 
 
 
Management Card 
User Manual 
 
 
 
Network Management Card
 – User Manual 
34003676EN/HA
 
Page 
42/81
 
 
Domain name is the domain to which the card belongs. This is the part of the full qualified domain name 
that follows the host name and is used by the DNS. The default value of the two parameters comprising the 
full qualified domain name: ups.domain.com 
 
TELNET connection: Authorises (choose enable) remote connection with a terminal to access the 
maintenance menu. 
See “
Configuration in local mode and via Telnet 
“ for more information 
 
BootP/DHCP: Authorises (choose enable) configuration of network parameters with your BootP/DHCP 
server when the card is booted  
Mode of card operation with server: after any reboot, if this option is enabled, the card tries to recover the 
network parameters from the server for 10 sec. If no response is received from the server, the card boots 
with the last saved parameters from the previous start. These parameters are those shown on the page  
The default value for this parameter is “Enable”  
 
. Note:  
The IP address supplied by the DHCP server must be fixed to maintain connection with the clients installed 
on the stations to be protected.  
 
 
Network Upgrade: Authorises (choose enable) remote upgrading of the embedded system on the card 
using the Mupgrade tool. Read the “
Maintenance
” section for more details. 
 
Primary DNS server: contains the IP address of the main DNS server ensuring conversion of the domain 
name to IP address. 
 
Secondary DNS server: contains the IP address of the secondary DNS server ensuring conversion of the 
domain name to IP address if the primary DNS server is not available. 
 
SMTP server: contains the name or IP address of the local server with which the card connects to send e-
mails. 
It may be filled in either as host + domain name (DNS resolution), or directly with the IP address  
The default value is stmpserver.domain.com . The card uses port 25 to send e-mails. 
 
The Authentication option must be selected if the SMPT server requires this parameter for query 
submission (see the RFC 2554 for SMTP authentication) for commercial reasons, access control, etc.  
When authentication is selected, the User and Password parameters must be specified for identification 
with the local SMTP server.  
Default values are MGEUPS/MGEUPS
 
Note: The card must be rebooted after any changes to these parameters.  See 
 “System”
 
 
Security: 
the administrator must click on Save and enter his login/password to save any modifications.