3.5.3 UPS Notified Applications
Click the “Notified Application” section in the menu.
Security: the administrator has to enter his login/password to view this information.
This menu enables:
Security: the administrator has to enter his login/password to view this information.
This menu enables:
◗
The addition of the supervision stations receiving traps and configuration of the trap type.
◗
To list all the Notified Applications and the main parameters.
◗
Simulate events to test notification and shutdown of the Notified Applications.
Up to 50 destinations can be managed by the card.
The card is compatible with the Network Shutdown Module
Note: It is not necessary to add the Network Shutdown Modules protecting your servers in this list as it is
done automatically.
The card is compatible with the Network Shutdown Module
Note: It is not necessary to add the Network Shutdown Modules protecting your servers in this list as it is
done automatically.
Select an entry in the list to modify the values in the edit zone at the bottom of the page. Note that the Network
Shutdown Module must not be manually modified.
The applications in the table appears in the order they have subscribed to the card. Following informations are
displayed :
◗
Nr : is the index where the application is stored into the table.
◗
Hostname or IP Address : By priority the hostname of the computer is displayed when the IP address can
be converted into a hostname with a DNS server or if the application has been entered as a hostname (see
page Network Management System settings). Otherwise the IP address is displayed.
be converted into a hostname with a DNS server or if the application has been entered as a hostname (see
page Network Management System settings). Otherwise the IP address is displayed.
◗
Application Name : sent by the application at subscribe time or manually entered.
◗
Output : is the number of the output from which the client is powered.
◗
Configuration : shows where the parameters of Network Shutdown Module comes from : Local(coming
from the application) or Central(coming from the card).
from the application) or Central(coming from the card).
◗
The Central Shutdown Configuration is available by clicking on Configuration link.
◗
Shutdown duration : is the shutdown duration necessary to properly shutdown the computer.