www.apc.com 
Status description 
Status to 0 
Status to 1 
Word 
hex 
Bit 
0 - F 
Status Familly 
for 
BMS design 
AC bypass thermal overload (Nota 7) 
No 
yes 
46 
Minor Fault 
AC Bypass out of tolerance (Nota 7) 
No 
yes 
46 
Major Warning 
AC bypass frequency out of tolerance (Nota 7) 
No 
yes 
46 
Minor Warning 
AC bypass voltage out of tolerance (Nota 7) 
No 
yes 
46 
Minor Warning 
AC bypass switch (Q4S) 
Open 
Closed 
46 
Status 
Static switch major fault (Nota 7) 
absent 
present 
47 
Minor Fault 
Inverter desynchronized with AC bypass 
absent 
present 
47 
Status 
Output switch (Q5N) 
Open 
Closed 
47 
Status 
Charger major fault 
No 
Yes 
49 
Minor Fault 
Battery charging (Nota 5) 
No 
Yes 
49 
3   
Status 
Inverter major fault (Nota 5) 
No 
Yes 
4C 
Minor Fault 
Inverter overload (Nota 5) 
No 
Yes 
4C 
Major Warning 
Inverter thermal overload (Nota 5) 
No 
Yes 
4C 
Minor Fault 
Inverter limitation (Nota 5) 
No 
Yes 
4C 
Status 
UPS fuse fault (Nota 5) 
absent 
Present 
4C 
Minor Fault 
Load Short circuit 
absent 
Present 
4F 
Minor Fault 
 
 
 
 
 
 
Nota 1 : for Battery charge it is necessary to set 2 bits, for legacy JBUS table 
Nota 3 : switch status equal  1, when closed 
Nota 4 :  
INMC/NMTC 
Galaxy 
@41 Hex 
@41 Bin 
@41 Bit3 
@41 Bit2 
@41 Bit1 
@41 Bit 1, 2 and 3 in Dec 
Unitary 
0010 
Modular 
0100 
Parallel 
0110 
SSC 
1000 
 
Nota 5 :  This Information is not present with a Static Switch Cabinet unit. 
Nota 6 : Device Ventilation Fault is present only in a Static Switch Cabinet 800kVA, this information is not present in a  Static Switch Cabinet 
1200kVA 
Nota 7 : For a configuration with UPS in parallel with SCC unit, the Main 2 data need to read on the card installed in the SSC unit. 
Nota 8 : Available with NMC firmware 808 and UPS package AN 
Nota 9 : Available with NMC fw 808 and G7000 package AM