• If the request was a read, and the read was performed successfully,
this will be indicated to the master by Resp1:Resp0 changing from 0:0
to 0:1. The parameter number response will equal the accessed
parameter number, and the resulting data read will be placed in the
data / error code response word.
to 0:1. The parameter number response will equal the accessed
parameter number, and the resulting data read will be placed in the
data / error code response word.
• If the request was a write, and the write was performed successfully,
this will be indicated to the master by Resp1:Resp0 changing from 0:0
to 1:0. The parameter number response will equal the accessed
parameter number, and the data written to the drive will be reflected in
the data / error code response word.
to 1:0. The parameter number response will equal the accessed
parameter number, and the data written to the drive will be reflected in
the data / error code response word.
• If an error occurred during the read or write request, this will be
indicated to the master by Resp1:Resp0 changing from 0:0 to 1:1.
The parameter number response will equal the parameter number
that the master was attempting to access, and an error code reflecting
the failure cause will be placed in the data / error code response
word. For a list of possible error codes, refer to section 10.4.
The parameter number response will equal the parameter number
that the master was attempting to access, and an error code reflecting
the failure cause will be placed in the data / error code response
word. For a list of possible error codes, refer to section 10.4.
6. In order to perform another parameter read or write, the master must once
again send a “no action” code (Req1=0 and Req0=0), and the PBDP-110
must once again respond with an idle state acknowledge (Resp1=0 and
Resp0=0) before the next read or write action can take place. Until a “no
action” code is sent to the PBDP-110, the interface will ignore all data in
the action bits, parameter number and parameter write data words. Also,
as long as the master sends the “no action” code, the PBDP-110 will loop-
back in the parameter number response word and parameter data / error
code response word whatever data is sent to it in the corresponding
output words.
must once again respond with an idle state acknowledge (Resp1=0 and
Resp0=0) before the next read or write action can take place. Until a “no
action” code is sent to the PBDP-110, the interface will ignore all data in
the action bits, parameter number and parameter write data words. Also,
as long as the master sends the “no action” code, the PBDP-110 will loop-
back in the parameter number response word and parameter data / error
code response word whatever data is sent to it in the corresponding
output words.
The above procedure explanation holds true for both drives A and B, using the
respective request and response locations in the output and input data
structures.
respective request and response locations in the output and input data
structures.
10.4 Register Access Error Codes
When a parameter read or write error occurs, one of the following error codes
will be returned in the parameter data response word:
Error Code
will be returned in the parameter data response word:
Error Code
Meaning
0x0000 ......................cannot
execute
0x0001 ......................data error (written data value outside of valid range)
0x0002 ......................invalid parameter number
0x0064 ......................attempt to write to a read-only parameter
0x0065 ......................attempt to read from a write-only parameter
0x0066 ......................other / unclassified error