TankGate responds to the following Function Codes:
There are two methods for data addressing within the TankGate
•The TankGate has a fixed Modbus Map of selected parameters
•Gateway Block (GWBLK) software blocks can be configured to set the data address
4.5.2
Fixed Modbus Map
For each version of the TankGate, there is a fixed map of data registers. A partial 
example is shown below:
Function Code
Description
Comments
3
Read Output 
Register
FC 3 and FC 4 are treated the same.  Use either FC 3 or FC 4 
to read data from the TankGate
4
Read Input 
Register
5
Force Single 
Output 
Status
FC 4 and FC 6 are treated the same.  Use either FC 5 or FC 6 
to write data to the TankGate
6
Preset Single 
Register
15
Force 
Multiple 
Outputs
FC 15 and FC 16 are treated the same.  Use either FC 15 or 
FC 16 to write multiple registers to the TankGate
16
Preset 
Multiple 
Registers
Address 
  Type 
Number 
Parameter      
Data Type 
5000
WV1900 
0
Command        
 CODED 
5001
WV1900
0
Level          
 REAL 
5003
WV1900
0
Temp           
 REAL 
5005
WV1900
0
Value          
 REAL 
5007
WV1900
0
Status         
 HEX 
5008
WV1900
0
PntStatus      
 IHEX 
5009
WV1900
0
Elapse         
 TIME 
5011
WV1900
1
Command        
 CODED 
5012
WV1900
1
Level          
 REAL 
5014
WV1900
1
Temp           
 REAL 
5016
WV1900
1
Value          
 REAL