Omron CS1W-RPT01 Manuale Utente

Pagina di 401
122
Setting Data Links
Section 5-2
(Data link start word – 1) + Total number of send/receive 
words in area 
247 (IR Area)
63 (LR Area)
5999 (DM Area)
6143 (EM Area)
c) Refer to the Controller Link Support Boards Operation Manual
(W307) for information on the Controller Link Support Board.
d) If CX-Net detects an error during the data link table check, trou-
bleshoot the error referring to 
Precautions
C200HX/HG/HE, CS/CJ-series, CVM1, CV-series, and CQM1H-series PLCs
have different-sized memory areas. When data links are manually set, pro-
vided the PLCs are set so as not to receive data in the areas indicated in the
following diagram, the data link setting area is not limited by the small area
size of the PLC.
If the LR Area in the C200HX/HG/HE or CQM1H Series is manually set for a
data link with a CVM1, CV-series or CS/CJ-series PLC, the LR words will be
linked to CIO 1000 to CIO 1063 in the CVM1, CV-series or CS/CJ-series PLC.
CIO 1064 to CIO 1199 cannot be linked with C200HX/HG/HE or CQM1H-
series PLCs in this way.
to
 
 
 
235
100 
 
 
 
335 
 
336
200 
 
 
 
435 
 
436
CVM1 and 
CV-series PLCs
C200HX/HG/HE and 
CQM1H-series PLCs
Example:
CS/CJ-series PLCs
Cannot be directly linked 
with C200HX/HG/HE or 
CQM1H words.
LR00
LR63
to
1000
1063
to
1064
1199
to
CVM1, CV-series or 
CS/CJ-series PLCs
C200HX/HG/HE and 
CQM1H-series PLCs