Omron CS1W-RPT01 Manuale Utente

Pagina di 401
229
Response Codes
Section 6-7
05: Routing error
01
Destination node address is not set in 
the routing table.
Set the destination node address in the 
routing table.
02
Routing table isn’t registered.
Set the source nodes, destination nodes, 
and relay nodes in the routing table.
03
Routing table error
Set the routing table correctly.
04
The maximum number of relay nodes 
was exceeded in the command.
Redesign the network or reconsider the 
routing table to reduce the number of relay 
nodes in the command. Use a CS/CJ-series 
CPU Unit with unit Ver. 2.0 or later with CX-
Programmer Ver. 4.0 or later to send com-
mands across three or more network levels.
10: Command format 
error
01
The command is longer than the max. 
permissible length.
Check the command format of the com-
mand and set it correctly.
02
The command is shorter than min. per-
missible length.
Check the command format of the com-
mand and set it correctly.
03
The designated number of data items 
differs from the actual number.
Check the number of items and the data, 
and make sure that they agree.
04
An incorrect command format has 
been used.
Check the command format of the com-
mand and set it correctly.
05
An incorrect header has been used. 
(The local node’s relay table or relay 
node’s local network table is wrong.)
Set the routing table correctly.
11: Parameter error
01
A correct memory area code has not 
been used or Extended DM Area is not 
available.
Check the command’s memory area code 
and set the appropriate code.
02
The access size specified in the com-
mand is wrong, or the first address is 
an odd number.
Set the correct access size for the com-
mand.
03
The first address is in an inaccessible 
area.
Set a first address that is in an accessible 
area.
04
The end of specified word range 
exceeds the acceptable range.
Check the acceptable limits of the data area 
and set the word range within the limits.
Check the data link tables to be sure the 
limit to link words has not been exceeded.
06
A non-existent program no. has been 
specified.
Check the program number and be sure 
that it is set correctly.
09
The sizes of data items in the com-
mand block are wrong.
Check the command data and be sure that 
the sixes of the data items are correct.
Check the data link tables to be sure all 
nodes in the refresh parameters are in the 
common link parameters.
0A
The IOM break function cannot be exe-
cuted because it is already being exe-
cuted.
Either abort the current IOM break function 
processing, or wait until it is completed and 
execute the command.
Check the data link tables for node 
addresses that have been set twice.
0B
The response block is longer than the 
max. permissible length.
Check the command format and set the 
number of items correctly.
0C
An incorrect parameter code has been 
specified.
Check the command data and reenter it cor-
rectly.
Check the data link table file for corruption.
Main code
Sub-
code
Probable cause
Remedy