Response Codes
Section 6-7
26: Command error
01
The specified area is not protected. 
This response code will be returned if 
an attempt is made to clear protection 
on an area that is not protected.
The program area is not protected, so it isn’t 
necessary to clear protection.
02
An incorrect password has been speci-
fied.
Specify a password that is registered.
04
The specified area is protected.
Execute the command again after executing 
the PROGRAM AREA PROTECT CLEAR 
command for the PLC.
To many commands at destination.
The destination has received more than 5 
commands. Either interrupt servicing or wait 
for servicing to complete before re-execut-
ing the command.
05
The service is being executed.
Execute the command again after the ser-
vice has been completed or aborted.
06
The service is not being executed.
Execute the service if necessary.
07
Service cannot be executed from local 
node because the local node is not part 
of the data links.
Execute the service from a node that is part 
of the data links.
A buffer error has prevented returning a 
normal response.
Reset the board. If the error persists, 
replace the board.
08
Service cannot be executed because 
necessary settings haven’t been made.
Make the necessary settings.
09
Service cannot be executed because 
necessary settings haven’t been made 
in the command data.
Check the command format of and make 
the necessary settings.
0A
The specified action or transition num-
ber has already been registered.
Execute the command again using an 
action or transition number that hasn’t been 
registered.
0B
Cannot clear error because the cause 
of the error still exists.
Eliminate the cause of the error and exe-
cute the ERROR CLEAR command.
30: Access right error
01
The access right is held by another 
node.
(Either a Programming Device at the 
other node is executing an SFC online 
edit, or the other node is executing an 
ACCESS RIGHT ACQUIRE or 
ACCESS RIGHT FORCED ACQUIRE 
command.)
Execute the command again after the 
access right has been released.
(The command can be executed after the 
ACCESS RIGHT FORCED ACQUIRE or 
ACCESS RIGHT RELEASE command is 
completed. Releasing the access right 
might affect processes in progress at the 
node that held the access right.)
40: Abort
01
Command was aborted with ABORT 
command.
---
Main code
Sub-
code
Probable cause
Remedy