Omron CS1W-RPT01 Manuale Utente
256
Data Link I/O Response Time
Section 8-3
CVM1, CV-series, CS/CJ-series PLCs Under Synchronous Operation or C200HX/HG/
HE and CQM1H-series PLCs
HE and CQM1H-series PLCs
Maximum I/O Response
Time
Time
The maximum data link I/O response time is calculated for four cases.
Case 1
The following diagram illustrates the data flow that will produce the maximum
data link I/O response time when the cycle time of the PLC at nodes #1 and 7
are greater than the communications cycle time.
data link I/O response time when the cycle time of the PLC at nodes #1 and 7
are greater than the communications cycle time.
There are four points shown in the diagram above where processing is
delayed, increasing the data link I/O response time.
delayed, increasing the data link I/O response time.
1,2,3...
1.
The input arrives in the PLC just after I/O refreshing, causing a delay of up
to one cycle before the input is read into the PLC.
to one cycle before the input is read into the PLC.
2.
Data exchange occurs just after the PLC at node #1 passes the token that
makes it the polling node, causing a delay of up to one communications cy-
cle time before the data is transferred in data link processing.
makes it the polling node, causing a delay of up to one communications cy-
cle time before the data is transferred in data link processing.
3.
At node #7, data from the previous data exchange is still being transferred,
causing a delay of up to one cycle before the input is read into the PLC.
causing a delay of up to one cycle before the input is read into the PLC.
4.
The data transferred in data link processing arrives at the PLC at node #7
after data exchange, so the data will not be read into the PLC until the next
data exchange, causing a delay of up to 1 to 2 cycle.
after data exchange, so the data will not be read into the PLC until the next
data exchange, causing a delay of up to 1 to 2 cycle.
The maximum number of words that can be exchanged in a single data ex-
change is approx. 7,800 words for CS/CJ-series PLCs, approx. 3,700
words for CVM1 and CV-series PLCs, approx. 4,000 for C200HX/HG/HE
PLCs, and approx. 1,200 words for CQM1H-series PLCs.
change is approx. 7,800 words for CS/CJ-series PLCs, approx. 3,700
words for CVM1 and CV-series PLCs, approx. 4,000 for C200HX/HG/HE
PLCs, and approx. 1,200 words for CQM1H-series PLCs.
Input device
Program
Program
Input
Input ON delay
1 cycle
Output
Output device
Output ON delay
1 cycle
Communications
cycle time
cycle time
Data link transmission
Controller Link Unit
transmission processing
transmission processing
PLC at node #7
(1)
I/O refresh
Data exchange
Controller Link Unit
transmission processing
transmission processing
PLC at node #1
Previous communica
tions cycle data
tions cycle data
Data link I/O response time
X
X
X
X
(2)
(3)
(4)
X