297
Status Area and Troubleshooting
Section 9-2
Other Status
Bit status
Probable cause
Probable remedy
Error log exists (CIO 1500 
+ 25 
× 
n, bit 15) is 1: ON
Error information on the 
Controller Link Unit (an 
error log) has been 
recorded.
Using the Controller Link 
Support Software or an 
FINS command, read the 
cause of the current error. 
Alternatively, use past error 
log records to troubleshoot 
the problem.
Communications controller 
send error (CIO 1500 + 25 
× 
n, bit 11) is 1: ON
The Controller Link Unit is 
faulty.
Replace the Controller Link 
Unit.
Inconsistent network 
parameters (CIO 1500 + 
25 
× 
n, bit 10) is 1: ON
Indicates that the network 
parameters recorded in the 
CS/CJ Bus Unit Area differ 
from the values of the Net-
work in use.
Check the network param-
eters on the Network in 
use using the Controller 
Link Support Software, and 
reset necessary parame-
ters.
Node address duplicate 
setting error (CIO 1500 + 
25 
× 
n, bit 9) is 1: ON
The same node address 
has been used more than 
once.
Reset so that each node 
address is used only once 
within the same Network.
EEPROM error (CIO 1500 
+ 25 
× 
n, bit 7) is 1: ON
An error has occurred 
while writing data to the 
CPU Unit’s EEPROM.
Check the status of bits 00 
to 02 in (CIO 1500 + 25 
× 
n, and correct any prob-
lems found. If the error 
occurs again, replace the 
CPU Unit.
PLC system setting error 
(CIO 1500 + 25 
× 
n, bit 3) 
is 1: ON
The CPU Unit’s EEPROM 
data is damaged.
Check the status of bits 00 
to 02 in (CIO 1500 + 25 
× 
n, and correct any prob-
lems found. If the error 
occurs again, replace the 
CPU Unit.
The PLC is protected.
Set the PLC’s protect 
switch to OFF.
Routing table error 
(CIO 1500 + 25 
× 
n, bit 2) 
is 1: ON
The routing table data 
within the CPU Unit’s 
EEPROM is damaged.
Refer to 7-4 Setting Rout-
ing Tables
 and reset the 
routing tables correctly. If 
the error occurs again, 
replace the Controller Link 
Unit.
There is an error in the 
routing table setting.
When using a routing 
table, refer to 7-4 Setting 
Routing Tables
 and reset 
the routing tables correctly.
If no routing tables are 
being used, delete the 
tables.