318
Error Log
Section 9-3
0117 
Hex
Internal buffer full
Command block 
Bits 0 to 7:
Source node address
Bits 8 to 14: 
Source Network address
Bit 15: 
OFF
Response block
Bits 0 to 7: 
Destination node 
address
Bits 8 to 14: 
Destination Network 
address
Bit 15: 
ON
(1st byte: bits 8 to 15; 
2nd byte, bits 0 to 7)
Increase number of 
retries or reconfig-
ure system to distrib-
ute load.
No
All
0118 
Hex
Illegal packet discarded
Check for nodes 
sending illegal 
packets.
Yes
All
0203 
Hex
EEPROM error
01 Hex: 
Read error
02: Hex: 
Write error
01 Hex: 
Data link 
tables
02 Hex: 
Network 
parameters
03 Hex: 
Routing 
tables
For CVM1 and CV-
series PLCs, check 
that the PLC is not 
protected.
Remake and set the 
relevant data. If the 
error occurs again for 
the CVM1 and 
CV-series, replace 
the CPU Unit and for 
the C200HX/HG/HE 
PLCs, replace the 
Controller Link Unit.
Yes
C200HX/HG/
HE, CV, 
CQM1H
0206 
Hex
Number of participating nodes 
decreased (local node still partic-
ipating)
Network 
parameters 
maximum 
node 
address
Number of 
non-partici-
pating nodes
Check network 
parameters, node 
participation, cables, 
and terminating 
resistance.
No
All
0207 
Hex
Number of participating nodes 
decreased (local node not partic-
ipating)
No
All
0208 
Hex
Polling node changed
Address of 
previous 
polling node
Address of 
new polling 
node
Check previous 
polling node.
No
All
0209 
Hex
Inconsistent network parameter 
00 Hex
Address of 
polling node
Using the Controller 
Link Support Soft-
ware, check network 
parameters.
Yes
All
020C 
Hex
Time out with token
00 Hex
Error status 
(See note.)
Check network 
parameters, node 
participation, cables, 
and terminating 
resistance.
No
All
0210 
Hex
Communications controller send 
error
00 Hex
Error status 
(See note.)
Replace the Control-
ler Link Unit.
Yes
All
0211 
Hex
Duplicate address error
00 Hex
Local node 
address
Reset so that each 
node address is used 
only once within the 
same Network.
No
All
0214 
Hex
Node address setting error
Not specified
Check the node 
address settings and 
correct them.
Yes
CS/CJ, 
CQM1H
Error 
code
Contents
Detail code
Correction
Written to 
EEPROM
Applicable 
PLC
1st byte
2nd byte