 Chapter 11 – Installing the system ground
Page 143 of 332
Option 11C Mini
Planning and Installation Guide
Figure 38
Grounding a Main Chassis and Chassis Expander pair
5
Connect the grounding block to the ground bus in the AC power 
service panel, using #6 AWG wire. See Table 26 on page 140 f
or 
region-specific grounding requirements.
6
Place a DO NOT DISCONNECT tag on the ground wire at the 
service panel.
7
Test the ground.
—————————— End of Procedure ——————————
WARNING
A qualified technician or electrician must make the connection in the 
AC power service panel.
Grounding lug
on Main Chassis
Ground
wire to the
Grounding lug
on Chassis
Expander 