 Chapter 3 — System and site requirements
553-3021-209
Standard 3.00
April 2000
The following are additional grounding requirements:
Ground conductors for the Option 11C Mini system:
— must not be smaller than #6 AWG (#40 metric) at any point (see 
Table 10 on page 49. This table provides a list of grounding wire 
requirements specific to some areas)
— must be routed through the same conduit as the phase conductors 
that serve the system
— must not be smaller than any phase conductor in the same conduit
— do not carry current under normal operating conditions
All ground conductors in the building:
— must be isolated from the neutral bus except at the service entrance 
to the building
— must be hardwired to the main ground reference
Avoid spliced conductors. Continuous conductors have lower 
impedance, and they are more reliable than spliced conductors.
CAUTION
Never connect the single point ground conductor from the Option 11C 
Mini system to structural steel members or electrical conduit. Never 
tie this conductor to a ground source or grounded electrode that is not 
hard-wired to the building reference conductor.