Chapter 7  Buffer read/write instructions 
 
7 - 10 
 
2)   Program example 
- Program that write 10 words, through the Fnet module mounted at the slot 02, from the 
D0200 ~ D0209 of self station to the address 11~20 of the buffer memory of the G3F-
AD3A module mounted at the slot 02 of remote station h0E. The link status will be stored 
at M020 of self station. 
 
 
[ System configuration ] 
 
Self-station 
   
 
 
 
 
 
 
 
 
 
GM4-
PA2A 
K4P-
15AS 
G4I-
D22A 
G4I-
D22A 
G4L-
FUEA 
Station 
No=h01
 
G4L-
FUEA 
Station 
No=h02
 
G4Q-
RY2A 
 
 
 
 
 
slot 0 
slot 1 
slot 2 
slot 3 
slot 4 
 
 
Remote station 
   
 
 
 
 
   
 
 
 
GM3-
PA2A 
G3L-
RBEA 
Station 
No=h0E
 
G3I-
D22A 
G3Q-
RY2A 
G3F-
AD3A 
 
 
 
 
   
 
slot 0 
slot 1 
slot 2 
 
 
 
 
 
 
 
[ Example program ] 
 
 
 
sl’ :   
upper byte 
à the code of remote module is hC0 
 
 
lower byte 
à slot number of Fnet module of self station is h02 
 
st’ : 
upper byte 
à slot number of remote A/D module is h02 
 
 
lower byte 
à the station number of remote station is h0E 
 
RPUT   hC002  h020E  D0200  00011  0010  M020 