Delta Electronics DVPDT02-H2 Dépliant

Pagina di 2
 
 
 
Warning 
 Please read this instruction sheet carefully before use and follow this instruction to operate the device in order to 
prevent damages on the device or injuries to staff.
 
 Switch off the power before wiring. 
 This instruction sheet only provides introductory information on electrical specification, functions, wiring, 
trouble-shooting and peripherals for DVPDT02-H2. Details of DeviceNet protocol are not included in this sheet. For 
more information on DeviceNet protocol, please refer to relevant reference or literatures.
 
 DVPDT02-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device 
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
 
 DVPDT02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it, only 
qualified professional staff familiar with the structure and operation of it can install, operate, wire and maintain it.
 
 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power, and DO NOT touch any terminal when the power is switched on. 
Make sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic interference
 Introduction 
Thank  you for choosing Delta  DVPDT02-H2 DeviceNet communication module. DVPDT02-H2 can be applied 
to the connection with DVP-EH2 series PLC MPU in a DeviceNet network.
 
 Features 
1.  Supports Group 2  only  servers. 
2.  Supports explicit connection in the pre-defined 
master/slave  connection  group. 
3.  The length of I/O data can be freely configured 
through  DeviceNet  network  configuration  tool. 
4.  Supports  polling. 
5.  Supports EDS files in DeviceNet network 
configuration  tools. 
6.  I/O data is extendable to 200 bytes. 
 Product Profile & Outline
 
 
PO WER
NS
MS
DR  1
DR  0
IN 0
IN 1
X
1 0
X
1 0
2
3
5
4
6
7
8
9
1
40  [1.575]
7
  
[0
.2
7
6
]
9
0
  
[3
.5
4
3
]
82  [3.228]
 
Unit: mm/[inch] 
 
1
 
Extension  port 
Node address setup rotary switch 
Function setup DIP switch 
POWER indicator 
MS  (Module Status)  indicator 
NS (Network Status) indicator 
DeviceNet  connector 
DIN rail 
DIN rail clip 
 
 Specifications 
DeviceNet Connector 
Type 
Removable  connector  (5.08mm) 
Transmission  method 
CAN 
Transmission  cable 
2 communication cables, 2 power cables, 1 shielded cable 
Electrical  isolation 
500V DC 
ENGLISH 
Communication 
Message  type 
I/O polling; explicit 
Series  transmission 
speed 
125kbps; 250kbps; 500kbps (bits per  second) 
Equipment type 
12 
Company ID 
799 (Delta Electronics, Inc.) 
Electrical Specifications 
Voltage:11 ~ 25V DC (supplied by the power cable in the network) 
DeviceNet 
Current: 28mA (typical), 125mA impulse current (24V DC) 
Environment 
Standards 
IEC 61131-2, UL508 
Storage/operation 
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity) 
Operation: 0ºC ~ 55 ºC (temperature), 50 ~ 95% (humidity), pollution degree 2 
Shock/vibration 
immunity 
International  standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 
68-2-27 (TEST Ea) 
Interference immunity 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
Certificates 
CE, UL 
 Components 
 DeviceNet Connector 
To connect to DeviceNet network,  use the  connector enclosed with DVPDT02-H2 or any connectors you can 
buy in the store for wiring. 
PIN 
Signal 
Color 
Description 
V- 
Black 
0V DC 
CAN_L 
Blue 
Signal- 
SHIELD 
Shielded cable 
CAN_H 
White 
Signal+ 
V+ 
Red 
24V DC 
 
1
2
3
4
5
 
 
 Node Address Setup Rotary Switch
 
The two rotary MAC ID setup switches set up the node  addresses  on  DeviceNet 
network in decimal form. Setup range: 00 ~ 63 (64 ~ 99 are forbidden) 
Rotary switch 
x 10
1
 
x 10
0
 
Multiple 
× 10 
× 1 
 
X
1 0
X
1 0
 
Example: If you need to set the node address of DVPDT02-H2 as 26, simply switch the corresponding rotary 
switch of x10
1
 to “2” and the corresponding rotary switch of x10
0
 to “6”. 
 
Switch setting 
Description 
0…63 
Valid DeviceNet MAC ID 
64…99 
Invalid DeviceNet MAC ID 
Note:
 The changed values on switches are only valid 
when DVPDT02-H2 is re-powered. When 
DVPDT02-H2 is operating, changing the set value of 
MAC ID will be invalid.
 
 Function Setup DIP Switch 
The function setup switches are for: 
1.  Setting up I/O data holding function (IN0) 
2.  Setting up the baud rates of DeviceNet network (DR0 ~ DR1) 
DR1 
DR0 
Baud rate 
OFF 
OFF 
125kbps 
OFF 
ON 
250kbps 
ON 
OFF 
500kbps 
ON 
ON 
Incorrect setting 
OFF 
When the DeviceNet connection is interrupted, the content in 
the buffer area will not be held. 
IN0 
ON 
When the DeviceNet connection is interrupted, the content in 
the buffer area will be held. 
IN1 
Reserved 
DR 1
DR 0
IN 0
IN 1
 
 Extension Port 
The  extension port  on DVPDT02-H2 is used for the connection to the next DVPDT02-H2 or extension  modules 
of DVP-EH2 series PLC MPU. 
 Basic Operation 
 Connecting DVPDT02-H2 to DVP-EH2 Series PLC MPU 
STOP
RUN
0
1
 
I N
OU T
P O W ER
R U N
E R R OR
B AT. L OW
D V P -20 E H
 
Switch off DVP-EH2. Open the connection port on the 
right hand side of DVP-EH2 and  connect DVPDT02-H2 to 
DVP-EH2. Switch on DVP-EH2, and DVP-EH2 will supply 
power  to DVPDT02-H2. There is no need to connect 
DVPDT02-H2 to an external power supply. 
 Install DVP-EH2 and DVPDT02-H2 on DIN Rail 
STOP
RUN
0
1
 
I N
OU T
P O WE R
R U N
E R R OR
B A T.L OW
D V P - 2 0E H
 
1.  Use 35mm DIN rail. 
2.  Open the DIN rail clips on DVP-EH2 and 
DVPDT02-H2. Insert DVP-EH2 and DVPDT02-H2 
onto the DIN rail. 
3.  Clip up the DIN rail clips on DVP-EH2 and 
DVPDT02-H2 to fix DVP-EH2 and DVPDT02-H2 on 
the DIN rail. 
As shown in the figure. 
 Connecting to DeviceNet Connector 
 
1.  The colors of the PINs on the DeviceNet connector 
match the colors of the connection cables. Make sure 
you connect the cable to the right PIN. 
2.  We recommend you also apply Delta’s power module 
in the  connection. 
As shown in the figure. 
 Installation & Wiring
 
1.  Install DVPDT02-H2 in an enclosure with sufficient space 
around it  to allow heat  dissipation (see the figure). 
2.  DO NOT place the I/O signal wires and power supply wire 
in the same wiring circuit. 
D>5 0 mm
DT0 2-H 2
D
D
D
D
EH 2 PL C
D
D
 
 Control Register 
The control registers (CR) are the registers inside DVPDT02-H2. See the table below for the definitions of all 
the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO instructions. 
CR# 
Attribute 
Content 
High byte 
Low byte 
#0 
Read 
Model name 
DVPDT02-H2 model code = H’0230 
#1 
Read 
Firmware  version 
Displaying the current firmware version in hex, e.g. V1.12 is 
indicated as H’0112. 
#2 
Read 
Length of I/O data 
Length of output I/O data 
Length of input I/O data 
#3 ~ #102 
Read/write  Input data mapping 
Area for storing data from DVPDT02-H2 to DeviceNet master 
#103 ~ #202 
Read/write  Output data mapping 
Area for storing data from DeviceNet master to DVPDT02-H2 
#203 ~ #215 
Set up by the system. DO NOT use it. 
#216 ~ #250 
Reserved 
#251 
Read 
Error 
Register for storing errors. See
 
 for error  codes. 
#252 ~ #254 
Reserved 
#255 
Read 
MPU status 
CR#255 = K0: MPU in STOP status 
CR#255 = K1: MPU in RUN status 
 LED Indicators & Trouble-Shooting 
There are 3 LED indicators on DVPDT02-H2. POWER indicator displays the status of working power. NS 
indicator and MS indicator display the connection status of the communication. 
 
NS LED 
LED status 
Indication 
How to deal with it? 
Off 
No power, or DVPDT02-H2 has not completed 
the Dup_MAC_ID test yet. 
1. Check the power of DVPDT02-H2 and see if the 
connection is normal. 
2. Check if the node communication on the network is 
normal. 
3. Make sure at least one or more nodes on the 
network are operational at the same time and the 
baud rate is the same as that of DVPDT02-H2. 
4. Check if the baud rate of DVPDT02-H2 is the same 
as that of other nodes. 
Green light 
flashes 
DVPDT02-H2 is on-line and has passed 
Dup_MAC_ID test but has not established 
connections to other nodes. 
  1. Correctly configure the slave module. 
  2. Re-download the configured data to the master and 
set the master PLC to be in RUN status. 
Green light on 
DVPDT02-H2 is on-line and is normally 
connected to the master. 
  -- 
Red light 
flashes 
DVPDT02-H2 is on-line, but I/O connections 
are timed-out. 
  1. Check if the network connection is normal. 
  2. Check if the master operates normally. 
Red light on 
The communication is down; MAC ID is 
repeated; no network power; bus-off 
1. Make sure all the MAC IDs on the network  are not 
repeated. 
2. Check if the network installation is normal. 
3. Check if the baud rate of DVPDT02-H2 is consistent 
LED status 
Indication 
How to deal with it? 
with that of the network. 
4. Check if the node address of DVPDT02-H2 is a 
valid one. 
5. Check if the network power is normal. 
 
MS LED
 
LED status 
Indication 
How to deal with it? 
Off 
No power 
Check the power of DVPDT02-H2 and see if the 
connection is normal. 
Green light 
flashes 
Waiting for I/O data; no I/O data; the program 
of DVPDT02-H2 is being edited. 
Switch DVPDT02-H2 to RUN status to start I/O data 
exchange. 
Green light on  I/O data are normal 
-- 
Red light 
flashes 
Recoverable  fault 
Re-power DVPDT02-H2 
Red light on 
Hardware  error 
1. Find out the cause of error in CR#251. 
2. Send back to the factory for repair if necessary. 
 
NS LED + MS LED
 
LED status 
NS LED 
MS LED 
Indication 
How to deal with it? 
Off 
Off 
No power 
Check the power of DVPDT02-H2 and see if the 
connection is normal. 
Off 
Green light 
on 
DVPDT02-H2 has not completed the 
Dup_MAC_ID test yet. 
Make sure at least one or more node on the network is 
operational at the same time and baud rate as the 
DVPDT02-H2 module. 
Red light 
on 
Red light 
flashes 
No network power 
1. Check if the network cable is correctly connected to 
DVPDT02-H2. 
2. Check if the network power works normally. 
Red light 
on 
Green light 
on 
Dup_MAC_ID test has failed; bus-off 
1. Make sure DVPDT02-H2 has a unique address.
 
 
2. Re-power DVPDT02-H2. 
Red light 
on 
Red light on  Hardware  error 
Send your DVPDT02-H2 back to the factory for repair. 
 
Error Codes
 
Code 
Description 
How to deal with it? 
00 
DVPDT02-H2 operates normally. 
-- 
E2 
I/O off-line 
1. Check if the network connection is normal. 
2. Check if the master operates normally. 
F0 
Dup_MAC_ID test has failed. 
1. Make sure DVPDT02-H2 has a unique address. 
2. Re-power DVPDT02-H2. 
F2 
Working power in low voltage 
Check if the power of DVPDT02-H2 and MPU is 
normal. 
F3 
Entering test mode 
Re-power DVPDT02-H2 
F4 
BUS-OFF 
Re-power DVPDT02-H2 
F5 
No network power detected 
1. Check if the network cable works normally. 
2. Check if the network power works normally. 
F7 
Internal error. GPIO detection error. 
Send your DVPDT02-H2 back to the factory for repair. 
F8 
Internal error. Manufacturing error. 
Send your DVPDT02-H2 back to the factory for repair. 
F9 
Internal error. Configured memory polling error. 
Send your DVPDT02-H2 back to the factory for repair. 
 
注意事項 
 
使用前請務必仔細閱讀本使用手冊,並依照本手冊指示進行操作,以免造成產品受損或人員受傷。 
 
配線時請務必關閉電源。 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅作為
DVPDT02-H2
操作指南和入門參考,DeviceNet 協定的詳細內容這裏不作介紹。如果使用者想瞭解更多
DeviceNet
協定的內容,請參閱相關專業文章或書籍資料。 
 
本機為開放型機殼,因此使用者使用本機時,必須將其安裝於具防塵、防潮及免於電擊∕衝擊意外的外殼配線
箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護人員操作或意外衝擊本體,造成
危險及損壞。 
 
本產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人員才
可進行本產品的安裝、操作、配線及維護。 
 
交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,且請
勿在上電時觸摸任何端子。本體上的接地端子    務必正確的接地,以提高產品抗雜訊能力。 
 
產品簡介 
謝謝您使用台達 DVPDT02-H2 網路通訊模組。DVPDT02-H2 定義為 DeviceNet 通訊模組,可用於 DeviceNet 網路
與 DVP-EH2 系列 PLC 主機的連接。 
 
功能特色 
1. 
支援 Group 2 only servers 
2. 
在預定義的主∕從連接組中支援顯性連接 
3.  I/O
資料長度可通過 DeviceNet 網路配置工具自由配置 
4. 
支援輪詢連接 
5. 
在 DeviceNet 網路配置工具中支援 EDS 檔 
6. 
連線 I/O 資料量最多可擴充 200 bytes 
 
產品外觀及各部介紹 
PO WER
NS
MS
DR  1
DR  0
IN 0
IN 1
X
1 0
X
1 0
2
3
5
4
6
7
8
9
1
40  [1.575]
7
  
[0
.2
7
6
]
9
0
  
[3
.5
4
3
]
82  [3.228]
 
尺寸單位:mm/[inch] 
1
 
擴充模組連接埠 
2
 
位址設定開關 
3
 
功能設定開關 
4
 
POWER 
指示燈 
5
 
MS (Module Status) 
指示燈 
6
 
NS (Network Status) 
指示燈 
7
 
DeviceNet
通訊連接器 
8
 
DIN
軌槽 
9
 
DIN
軌固定扣 
 
 功能規格 
DeviceNet
連接器 
接頭 
可插拔式連接  (5.08mm) 
傳輸方式 
CAN
 
傳輸電纜 
2
條通訊線、2 條電源線、1 條遮罩線 
電氣隔離 
500V DC
 
通訊 
繁體中文 
資訊類型 
I/O
輪詢  顯性 
串列傳輸速度 
支援 125kbps; 250kbps; 500kbps(位
秒) 
設備類型 
12 
廠商 ID 
799
(台達電子) 
電氣規格 
電壓規格:11 ~ 25V DC(由網路中的電源線提供) 
DeviceNet 
電流規格:28mA(典型值)、125mA 衝擊電流 (24V DC)  
環境規格 
標準 
IEC 61131-2
、UL508 標準 
操作∕儲存環境 
儲存:-25ºC ~ 70ºC(溫度)、5 ~ 95%(濕度) 
操作:0ºC ~ 55 ºC(溫度)、50 ~ 95%(濕度)、污染等級 2 
耐震動∕衝擊 
國際標準規範  IEC 61131-2、IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) 
雜訊免疫力 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
認證專案 
CE
認證、UL 認證 
    各部分元件介紹 
 DeviceNet
通訊連接器 
與 DeviceNet 網路連接時,可使用 DVPDT02-H2 隨機附帶的連接器或市售的連接器進行配線。 
接腳 
信號 
顏色 
敍述 
V- 
黑色 
0V DC
 
CAN_L 
藍色 
Signal-
 
SHIELD 
-
 
遮蔽線 
CAN_H 
白色 
Signal+
 
V+ 
紅色 
24V DC
 
 
1
2
3
4
5
 
 
位址設定開關 
兩個旋轉式位址設定開關以十進位形式設定 DeviceNet 網路上的節點位址。設定
範圍:00 ~ 63(64 ~ 99 不可用)。 
位址開關 
x 10
1
 
x 10
0
 
倍率 
× 10 
× 1 
 
X
1 0
X
1 0
 
例:若用戶需將 DVPDT02-H2 的節點位址設置為 26 時,只要將 x10
1
對應的旋轉開關旋轉到 2,再將 x10
0
對應
的旋轉開關旋轉到 6 即可。 
位址設定 
說明 
0 ~
 
63 
有效的 DeviceNet 通訊位址 
64
 
~ 99 
無效的 DeviceNet 通訊位址 
    
注意:位址設定開關的設定值變化後,只有在
DVPDT02-H2
重新上電啟動後才會生效。當
DVPDT02-H2
運行時,變更位址設定值是無效的。