Chapter 7  Troubleshooting |VFD-S Series 
7-6 
Revision August 2006, SE08, SW V2.61 
7.9 Motor cannot Run 
 
 
 
Motor cannot run
  Check PU01 
    for normal
     display
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Check if non-fuse 
breaker and magnetic
contactor are ON
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Set them to ON
Reset after clearing
fault and then RUN
Check if there is any 
fault code displayed
Check if input
voltage is normal
Check if any faults 
occur, such as
Lv, PHL or 
disconnection
Input "RUN" 
 command
 by keypad
It can run when
no faults occur
If jumper or DC 
reactor is connected
between +1 and +2/B1 
Use jumper
or DC reactor
Press RUN key to 
check if it can run
Maybe AC motor drive has malfunction or misoperation
due to noise. Please contact DELTA.
Press UP key to 
set frequency
Yes
Modify frequency
setting
Check if input FWD
or REV command
Check if the wiring 
of terminal FWD 
and between 
REV-DCM is correct
Yes
Change switch or relay
Set frequency or not
Press UP to 
check if motor 
can run
Correct connection
Check if the parameter 
setting and wiring of 
analog signal and
multi-step speed 
are correct
No
Motor has malfunction
No
Maybe AC motor drive has malfunction.
Please contact DELTA.
Check if there is any 
output voltage from 
terminals U, V and W
Check if motor 
   connection
    is correct
No
Connect correctly
Check if the setting
        of torque 
    compensation
        is correct
Increase the setting of
torque compensation
Motor is locked due to large load, please reduce load.
For example, if there is a brake, check if it is released.
If load is too large
if upper bound freq. 
and setting freq. is 
lower than the min.
output freq.
Yes
Change defective
potentiometer and 
relay
Yes