DVP-PCC01
 
Program Transfer Module 
Instruction Sheet 
 
1  
Warning 
Please set the RD/WR switch before operating the . 
Do not disconnect PCC01 before Transmission ends; otherwise, it may cause data loss in the PCC01 
Do not change the RD/WR switch during PCC01 operation. 
2  
Introduction 
 
PCC01 can read or write PLC programs, devices (coils and registers) and passwords to all series of PLC via 
COM. It provides rapidly and safely data transmission to PLC. 
 
Applicable Models and Read/Write Device Types: 
Program area   
PLC device area 
Device type 
Models 
Program (Steps) 
D register 
M device 
File register 
DVP-ES/EX/EC/SS 4K 
D0~D599 M0~M1279 
N/A 
DVP-SA/SX/SC 8K D0~D4999 
M0~M4095 
1600 
DVP-EH/SV 16K 
D0~D9999 
M0~M4095 
10000 
 
Product Profile 
 
PO
WE
R
OK
CO
M
ER
A
S
E
D
VP-
PC
C
0
1
ER
R
5
6
33
66.3
300
1
2 3
4
WR
RD
 
 
Unit: mm 
1. Power LED 
4. Error LED 
2. Communication Indicator LED 
5. Operation mode: read/write functional switch 
3. Operation completed LED 
6. PCC01 Data Erase button 
 
Specification 
Data Retention 
10 years 
Write Cycles 
At Least 10,000 times 
Transmission speed 
9600 /19200 bps (PB: 9600 bps only) 
Storage  
-25℃~70℃  (Temperature), 5~95% (Humidity) 
Operation 
0℃~55℃  (Temperature), 50~95% (Humidity), Pollution degree 2 
Noise Immunity 
ESD:  ±4KV Air Discharge 
EFT: Power Line: 2KV 
RS: 0.15MHz~80MHz, 10V/m 
Surge :  ±1KV 
Vibration / Shock 
Resistance 
International Standard: IEC1131-2, IEC 68-2-6(TEST Fc) 
IEC1131-2 & IEC 68-2-27 (TEST Ea) 
 
3   
Operation and Function Description 
3.1 Read/Write Operation Sequence: 
Step 
 (PLC→PCC01) RD (Read) 
 (PLC←PCC01) WR (Write) 
Set RD/WR switch to “RD” mode 
Set RD/WR switch to “WR” mode and confirm PLC 
is STOP status 
Connect PCC01 to PLC COM1.Reading will start 
after 5sec. waiting. 
Set RD/WR switch to “WR” mode and place the 
PLC RUN/STOP switch in the STOP position. 
After reading data from PLC, “OK” LED will light 
Connect PCC01 to PLC COM1.Writing will start 
after 5 sec. 
Disconnect PCC01 when read process is done. 
Disconnect PCC01 when write process is done. 
3.2 Password 
Function 
 
The PCC01 transfer module can obtain a password from the source PLC along with the program. When the 
program is transferred from the ACPGMXFER to the destination PLC it will compare the password and if the 
password in the PLC matches or no password was previously set the transfer will complete. This will require 
future ACPGMXFER transfers to a password protected PLC to have the same password as the PLC, Also if a 
password is set via the transfer module any WPLSOFT users will be required to enter the password before any 
program changes can be made.   
 
The password is entered into registers D1086 and D1087 and set on by enabling M1086. These addresses 
serve only as an entry point for the password at the source PLC. When the file is ‘Wrote’ to the destination PLC 
the unit will be password protected and registers D1086 and D1087 will not be populated with the password. If 
M1086 is not set on the passwords will be ignored.   
 
The password is set in the source PLC by using the Batch Monitoring feature of the PLC software or hand held 
programmer to enter the password into registers D1086 and D1087. Enter the value in Hexadecimal format, a 
password of 1234 would be entered as follows. H3132 into register D1086 followed by H3334 into register 
D1087. Refer to the table in section 6 for cross reference of valid ASCII characters. Next set M1086 on to make 
this password active.   
 
Connect the transfer module to the source PLC with the switch set to read. This will upload the program and the 
password of 1234. The destination PLC will have to be in the stop mode, next connect the transfer module to 
the destination PLC with the switch set to the “write” position. The transfer module will download the program 
and set the password to 1234. 
 
The password key has four digits. Each digit is 8bits number and form with ASCII in D1086 and D1087. 
Example as follows: 
D1086 
D1087 
     Password Key 
Password setting 
High byte 
Low byte 
High byte 
Low byte 
Byte 1 
Byte 2 
Byte 3 
Byte 4 
ASCII code (HEX) 
1 (0x31=H31) 
2 (0x32=H32) 
3 (0x33=H33) 
4 (0x34=H34) 
3.3  The conditions when PCC01 will read/write to an PLC:(w/ PW: with password; w/o PW: without password) 
Read 
Write 
                              PCC01
PLC Status 
w/o PW 
w/ PW 
w/o PW 
w/ PW 
w/o PW
Able to read 
Password verify error
Unable to write 
Unable to write 
RUN 
w/ PW 
Unable to read 
Unable to read 
Unable to write 
Unable to write 
w/o PW
Able to read 
Password verify error
Able to write 
Able to write and 
write password to 
PLC 
STOP 
w/ PW 
Unable to read 
Unable to read 
Password verify error
Able to write after 
verification 
3.4  PCC01 force PLC in RUN/STOP status 
PCC01 provide Run/Stop function in DVP-ES/EX/EC series MPUs. When PCC01 ERR and OK LEDs are blinking 
simultaneously in WR mode and PLC is in RUN status, user can press the ERASE button within 30 seconds to force 
PLC in STOP After that, disconnect PCC01 from the PLC and then connect to PLC again. Once data write-in is 
completed, push ERASE within 30 seconds while PCC01’s OK LED is ON to switch PLC status from STOP to RUN. 
3.5  PCC01 Data Erase function: 
Once PCC01 connects to PLC, please press and hold the ERASE button within 5 secs. Continue to hold the button 
until the OK LED turns on. Release the button and the ACPGMXFER module can now be removed. 
3.6  Data Duplication Function 
 
Besides program transfer, the PCC01 can also read/write register and coil data to/from the PLC. The PCC01 
will monitor coil M1085 to see if it should read/write the data.    When M1085 is OFF, the PCC01 will read or 
write the data depending on the operation selected. If M1085 is ON he PCC01 will not read or write the data.   
 
Data Duplication steps:   
1.) Set M1085 On/Off in PLC 
2.) Select PCC01 RD/WR switch in reading or writing mode.   
3.) Connect PCC01 to PLC COM1 communication port 
4.) After operation is completed, “OK” LED will turn on. 
5.) Disconnect PCC01 from the PLC. 
3.7  Estimation of Read/Write Operating Timing 
 
M1085=OFF 
M1085=ON 
Model 
Read 
Write 
Read 
Write 
DVP-ES/EX/SS 
35 sec. 
45 sec. 
30 sec. 
35 sec. 
DVP-SA/SX/SC 
1 min. 10 sec. 
1 min. 15 sec. 
1 min. 5 sec. 
1 min. 10 sec. 
DVP-EH/SV 
2 min. 50 sec. 
3 min. 
1 min. 10 sec. 
1 min. 20 sec. 
 
4  Error 
Indication 
PCC01 will show an error or warning status with the ERR and OK LEDs. 
 
Below is the summary: 
Indicator 
Error Message 
ERR 
OK 
Recommend 
 
 
PCC01 Internal memory 
error 
On Off 
PCC01 hardware may be damaged, please replace it. 
 
 
Incompatible model 
Blinking Off 
Make sure PCC01 model record is compatible with PLC 
model. 
 
 
Operation error – unable 
to write 
Synchronous blinking 
PCC01 doesn’t contain a valid program for “WR” mode. 
PCC01 in “WR” mode, and PLC is in RUN mode. Please 
place PLC in STOP mode. 
Communication protocol error! Please confirm the PLC is in 
STOP mode and reboot the PLC. 
Check PLC program syntax. 
 
 
Operation error – unable 
to read 
Cross blinking 
PLC protect with password. 
Communication protocol error! Please confirm PLC in STOP 
mode and remove/apply power to. 
 
 
Password verify error 
On Blinking 
PCC01 is in “RD” mode, and is protected by password. 
Please push erase button when PCC01 connect to the PLC. 
For more detailed operation of erasure, please reference to 
section 3.4. 
PCC01 is in “WR” mode, and PLC is protected by password. 
Please disable the password in PLC, or set the same PLC’s 
password in the PCC01. For more detailed operation , please 
reference to section 3.2. 
 
 
ERASE completed 
Off On 
Please refer to section 3.5. 
 
5  Troubleshooting 
 
If ERR LED is always ON or blinking. Please refer to section 4.   
 
Disconnecting the PCC01 or powering down the PLC when the operation in progress will cause unexpected 
results: 
 
PCC01 in “RD” mode: 
PCC01 data will be invalid. Please reboot the PLC again or re-connect PCC01 to PLC. 
 
PCC01 in “WR” mode: 
PLC program will be invalid. Please reboot PLC again or re-connect the PCC01 to PLC. 
 
6  Appendix: 
ASCII 
Table 
The password composed of 4 bytes. Each byte is an ASCII character of ‘0’~’9’, ‘A’~’Z’. ‘a’ ~’z’. The password is case 
sensitive. Below is ASCII table. 
HEX
A
B
C
D
E
ASCII
 
 
 
 
 
 
HEX
10
11 
12 
13 
14 
15 
16 
17
18
19
1A
1B
1C
1D
1E
1F
ASCII
 
 
 
 
 
 
HEX
20
21 
22 
23 
24 
25 
26 
27
28
29
2A
2B
2C
2D
2E
2F
ASCII
SP
! " # $ % & ' ( ) * + , - . / 
HEX
30
31 
32 
33 
34 
35 
36 
37
38
39
3A
3B
3C
3D
3E
3F
ASCII
0 1 2 3 4 5 6 7 8 9  :  ;  < = > ? 
HEX
40
41 
42 
43 
44 
45 
46 
47
48
49
4A
4B
4C
4D
4E
4F
ASCII
@
A B C D E F G
H
I  J K
L M
N
O
HEX
50
51 
52 
53 
54 
55 
56 
57
58
59
5A
5B
5C
5D
5E
5F
ASCII
P
Q R S T U V W
X
Y
Z ⌧
HEX
60
61 
62 
63 
64 
65 
66 
67
68
69
6A
6B
6C
6D
6E
6F
ASCII
` a b C d e f g h i  j k l M
n o 
HEX
70
71 
72 
73 
74 
75 
76 
77
78
79
7A
7B
7C
7D
7E
7F
ASCII
p q r s t u v w x y z {  |  } ~ ⌧
Note: ‘⌧’:Denotes invalid ASCII character, do not use.