Input Calibration 
4/07 
UDC2500 Universal Digital Controller Product Manual 
137 
Calibration Steps 
Use the following steps when calibrating an input. 
Step 
Action 
Find the minimum and maximum range values for your PV input range from Table 5-1. 
Disconnect the field wiring and find out what equipment you will need to calibrate. 
Wire the calibrating device to your controller according to the set up wiring instructions 
for your particular input (Subsection 5.4 or 5.6). 
Follow the calibration procedure given for Input #1 or Input #2 (Subsection 5.5 or 5.7). 
5.2  Minimum and Maximum Range Values 
Select the Range Values 
Calibrate the controller for the minimum (0 %) and maximum (100 %) range values of 
your particular input type. Two input controllers will need to have each input calibrated 
separately. 
Select the Voltage, Current or Resistance equivalents for 0 % and 100 % range values 
from Table 5-1 and Table 5-2. Use these values when calibrating your controller. 
Table 5-1  Voltage, Milliamp and Resistance Equivalents for Input 1 Range Values 
PV Input Range 
Range Values 
Sensor Type 
°F 
°C 
0 % 
100 % 
Thermocouples 
(per ITS-90) 
 
 
 
 
B 
 
  0  to  3300 
 
–18  to  1816 
–0.100 mV 
13.769 mV 
  –454  to  1832 
  –270  to  1000 
–9.835 mV 
76.373 mV 
E (low) 
  –200  to  1100 
  –129  to  593 
–6.472 mV 
44.455 mV 
 
0  to  1600 
 
–18  to  871 
–0.886 mV 
50.060 mV 
J (med) 
20 to 900 
–7  to 482 
–0.334 mV 
26.400 mV 
J (low) 
20 to 550 
–7 to 288 
–0.334 mV 
15.650 mV 
0 to  2400 
–18 to 1816 
–0.692 mV 
52.952 mV 
K (med) 
–20 to 1200 
–29 to 649 
–1.114 mV 
26.978 mV 
K (low) 
–20 to 750 
–29 to 399 
–1.114 mV 
16.350 mV 
NiMo-NiCo (NM90) 
32 to 2500 
 
0  to 1371 
0.000 mV 
71.773 mV 
NM90 (low) 
32 to 1260 
 
0  to  682 
0.000 mV 
31.825 mV 
 Nicrosil-Nisil (Nic) 
 
0  to  2372 
 
–18  to 1300 
–0.461 mV 
47.513 mV 
Nic (low) 
 
0  to  1472 
 
–18  to  800 
-0.461 mV 
28.455 mV 
 
0  to  3100 
 
–18  to 1704 
–0.090 mV 
20.281 mV