UDC2500 Universal Digital Controller Product Manual 
4/07 
Function Prompt  
Lower Display 
Selection or Range of 
Setting  
Upper Display 
English 
Numeric 
Code 
English 
Numeric 
Code 
Parameter  
Definition 
TX_DLY 1005  1 to 500 
milliseconds 
 
TX DELAY—Configurable response-delay timer 
allows you to force the UDC to delay its response 
for a time period of from 1 to 500 milliseconds 
compatible with the host system 
hardware/software. This parameter is also used for 
the IR communications link. 
WS_FLT 1006   
 
 
 
 
 
 
FP B 
FPBB 
FP L 
FPLB 
 
 
 
 
 
 
 



Defines word/byte order of floating point data for 
communications.  Byte values: 
 
         0                1                         2                     3 
seeeeeee emmmmmmm mmmmmmmm mmmmmmmm
  
Where: 
   s = sign, e = exponent, m = mantissa bit 
 
    0                1                         2                     3 
    1                0                         3                     2 
    3                2                         1                     0 
    2                3                         0                     1 
SDENAB 1007  DIS  
ENAB 

SHED ENABLE—Disables/enables shed 
functionaliy.  
SHDTIM 1008  0 to 255 
Sample 
Periods 
 
SHED TIME—The number that represents how 
many sample periods there will be before the 
controller sheds from communications. Each 
period equals 1/3 seconds; 0 equals No shed.  
Note: If ComSTA is set to MODBUS and if 
SHEDENAB is set to DISABL, Shed Time will not 
be configurable. 
SDMODE 1009   
 
SHED CONTROLLER MODE AND OUTPUT 
LEVEL
—Determines the mode of local control you 
want when the controller is shed from the 
communications link.  
 
 
LAST 0 
LAST—SAME MODE AND OUTPUT—The 
controller will return to the same mode (manual or 
automatic) at the same output level that it had 
before shed. 
 
 
MAN 1 
TO MAN—MANUAL MODE, SAME OUTPUT—
The controller will return to manual mode at the 
same output level that it had before shed. 
 
 
FSAFE 2 
FSAFE—MANUAL MODE, FAILSAFE OUTPUT—
The controller will return to manual mode at the 
output value selected at Control prompt FAILSAFE.