ADC ComProtect Dépliant

Pagina di 2
Website: www.adc.com
From North America, Call Toll Free: 1-800-366-3891 • Outside of North America: +1-952-938-8080
Fax: +1-952-917-3237 • For a listing of ADC’s global sales office locations, please refer to our Website.
ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, Minnesota  USA  55440-1101
Specifications published here are current as of the date of publication of this document. Because we are continuously 
improving our products, ADC reserves the right to change specifications without prior notice. At any time, you may 
verify  product  specifications  by  contacting  our  headquarters  office  in  Minneapolis.  ADC  Telecommunications,  Inc. 
views its patent portfolio as an important corporate asset and vigorously enforces its patents. Products or features 
contained herein may be covered by one or more U.S. or foreign patents. An Equal Opportunity Employer
104560AE  5/08  Revision  ©  2008   ADC Telecommunications, Inc.  All Rights Reserved
Spec 
Sheet
O r d e r i n g   I n f o r m a t i o n
Description
Catalog Number
ComProtect GDT 2/1 CP TP280A1 - Quantity: 1 (Pack of 100)
PRO-6659 1 509-30B
Gel ComProtect GDT 2/1 CP TP280G1 - Quantity: 1 (Pack of 100)
PRO-6659 1 509-30G
Technical Specifications
  DC Sparkover 
350 V ±20%@ 100V/s
1
  Impulse Sparkover 
625 V @ 100V/µs
    
875 V @ 1,000V/µs
  Insulation Resistance 
>10
10
Ω @ 100V
  Impulse Discharge Current 
40,000 A, 8/20 µs (1 operation minimum)
    
20,000 A, 8/20 µs (>10 operations)
    
1,000 A, 8/20 µs (>400 operations)
  Alternating Discharge current 
130 A
rms
, 11 cycles (1 operation minimum)
    
20 A
rms
, 1s (> 10 operations) 
  Bit Error Rate (BER) 
< 10
-7
  Longitudinal Balance 
> 52 dB up to 16 MHz, > 40 dB up to 100 MHz
  Operating Temperature 
-40°C to +85°C (-40°F to +185°F)
  Housing material 
UL 94 V-0
 
1
 DC Sparkover may exceed ±25% after discharge, but will continue to protect without venting.
ComProtect
® 
Gas Discharge Tube 
Single-Pair Protectors For Series 2 Switching Blocks
S2 Block
30.5 mm
69.9 mm
29 mm
23.5 mm
Ground Bar
21.3 mm
9.4 mm
9.4 mm
21.3 mm
47.3 mm
29 mm
ComProtect dimensions
Inserted ComProtect
INSERTION LOSS
dB
frequency range
< 0.01 dB
up to 16 MHz
< 0.025 dB
16 - 31.25 MHz
< 0.07 dB
31.25 - 42.6 MHz
< 0.15 dB
42.6 - 100 MHz
RETURN LOSS
dB
frequency range
> 37 dB
up to 20 MHz
> 25 dB
20 - 62.5 MHz
> 19.5 dB
62.5 - 100 MHz