Chapter 7
Advanced Application Topics
© National Instruments Corporation
7-11
4.
Run the VI. Because the Product tag is configured to go into HI alarm 
when it exceeds a value of 800, you can see that the tank color is blue 
while the tag value is below 800. It changes from blue to red when the 
value goes above 800. Leave this VI running.
5.
To change the HI alarm limit of Product dynamically, open a new VI. 
Drop the Set Tag Attribute VI from the Functions»Tag Attributes 
palette.
6.
Using the wiring tool, create constants for the group/tag namestag 
attribute
, and value inputs.
7.
Select Product for the group/tag names input, change tag attribute 
from the default 
<none>
 to 
HI Limit
, and wire in 
500.00
 for the 
value as shown in the following illustration.