Important Safety Instructions
IPD4-A2-ZZ40-20
 4000E IP Broadband Loop Carrier Installation Instructions
19
Important Safety Instructions
Read and follow all warning notices and instructions marked on the 
product or included in the manual.
Do not attempt to service this product yourself, as opening or removing 
covers may expose you to dangerous high voltage points or other risks. 
Refer all servicing to qualified service personnel.
3 WARNING: This unit supports a redundant 48 VDC power input 
connection. Disconnect both sources of input power before servicing.
This product is to be installed only in a Restricted Access Location 
(dedicated equipment rooms, equipment closets or the like) in accordance 
with articles 110-16, 110-17 and 110-18 of the National Electrical Code, 
ANSI/NFPA 70.
This product is to be connected to a 48 VDC SELV supply source that is 
electrically isolated from the AC source.
The positive terminal of the 48 VDC source is to be reliably connected to 
earth. Connect a green/yellow earthing (grounding) wire to the protective 
earthing (grounding) lug connector, identified by the protective earth 
symbol on the chassis.
A readily accessible disconnect device as part of the building installation 
shall be incorporated in fixed wiring. The disconnect device (a 48 VDC, 
10 A, single pole circuit breaker or switch) must be included in the 
ungrounded supply conductor. Over current protection must be included 
with a 48 VDC, 10 A fuse or circuit breaker in the ungrounded conductor. 
Use minimum 16 AWG (2.5 mm
2
) fixed power source wires with strain 
retention.
Do not allow anything to rest on the power cord and do not locate the 
product where persons will walk on the power cord.
Slots and openings in the cabinet are provided for ventilation. To ensure 
reliable operation of the product and to protect it from overheating, these 
slots and openings must not be blocked or covered.
10 General purpose cables are described for use with this product. Special 
cables, which may be required by the regulatory inspection authority for 
the installation site, are the responsibility of the customer. To reduce the 
risk of fire, use a UL Listed or CSA Certified, minimum No. 26 AWG 
(0.128 mm2) telecommunication cable, or comparable cables certified for 
use in the country of installation.
11 A rare phenomenon can create a voltage potential between the earth 
grounds of two or more buildings. If products installed in separate 
buildings are interconnected, the voltage potential may cause a hazardous 
condition. Consult a qualified electrical consultant to determine whether 
or not this phenomenon exists and, if necessary, implement corrective 
action prior to interconnecting the products.
12 In addition, if the equipment is to be used with telecommunications 
circuits, take the following precautions:
— Never install telephone wiring during a lightning storm.
!