Interface to the User Program in the S7-200 CPU
2-22
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Banks 2–15: Command data on the AS-Interface
Via this area, you can store command calls on the CP 243-2. The data structures
and codes used are described in Section 5.2. The number of banks used depends
on the particular command.
Banks 16–30: Reserved area
These areas are reserved for later expansions and cannot be used.
Bank 31: Binary output data of the AS-i slaves 1B – 31B
Using these analog output words, you can access the binary outputs of the B
slaves (slaves with the extended addressing mode).
The structure of the output data is described in Section 3.1.2.
Banks 32–47: Analog output data of the AS-i slaves
Via these areas, you can access the analog binary outputs of AS-i slaves that
support the AS-i slave profile 7.3 or 7.4 (see Section 3.1.2).
Banks 48–63: Reserved area
These areas are reserved for later expansions and cannot be used.