Chapter 4: E2 Controller
NOTE: You may turn the A/C unit on and off at any time by pressing and holding the Enter key for 3 seconds.
Other status messages that may appear at the bottom of the screen are:
“OFF by remote shutdown” indicates the Remote Start/Stop feature is enabled and requires a remote start switch to be turned 
On.
“OFF by Network” indicates the unit is part of a group and is off because of a grouping priority command such as a compressor 
alarm or loss of airflow, or the BMS communication feature is enabled and the unit received a network signal to pause operation.
“OFF by Internal Alarm” indicates that the unit is off because of a group alarm condition. (Only active with grouped units.)
“Unit on CL Lockout” indicates cooling has been locked out while there is a demand for dehumidification because the  
temperature is below the minimum temperature allowable for dehumidification (factory default setting is 4° F below setpoint).
4.  After the initialization period expires, the controller enables the control output to the fluid control valve (CRDX-W-FS-12KW, 
CRDX-W-FS-24KW, CRDX-G-FS-12KW, CRDX-G-FS-24W) and the fans are allowed to begin operating.
5.  The Black Box logo in the display is replaced with a blower 
 symbol. The fans begin operating in stages with five-second 
time delays. The middle fan starts first, then the upper fan, then the lower fan.
6.  Following a 45-second time delay (after the first fan turns on), the controller polls the air proving switch. If adequate airflow is 
detected, the controller enables the compressor to turn on if there is a demand for cooling or dehumidification as defined by 
the control setpoints.
Figure 4-13. Controller polls screen.
7. The controller records the date and time power is reinitialized in the alarm history log.
8.  If the actual room conditions are not within the range of the programmed setpoints, the system will begin operating in the 
mode(s) needed to reach the setpoints (cooling or dehumidifying). Symbols appear to indicate the active operating modes.
 = Blower On
 = Call For Cooling
 = Dehumidifying
9.  Temperature and humidity alarms are masked out for 30 minutes to allow conditions to stabilize without triggering nuisance 
alarms.
10.  Operator interface to the menu loops is available from the Main screen by pressing the Program (Prg) key. The controller starts 
a timer whenever a key sequence is initiated. Every time a button is pressed, the timer is reset. If there is no key activity for 60 
seconds, the controller will return to the Main screen unless the Screen Lock feature is enabled in the Information menu loop 
(see Section 4.5.2).
4.3.1 Setpoint Adjustment
1. From the Main screen, access the Main Menu screen by pressing the program 
 key.
2.  Scroll through the Main Menu selections with the Up   and Down   arrow keys and select the Control menu by pressing the 
Enter 
 key when “CONTROL” appears in bold letters in the center of the screen. A password entry screen will be displayed.
3. To access the Control menu, press the Enter 
 key twice to insert a flashing cursor in the “Enter Password” field.