Chapter 4: E2 Controller
4.5.3.4 Alarm Screen Messages
Table 4-3. Alarm screen messages.
Alarm Release
Description of Alarm Conditiion
High Temperature
Air temperature is above user-defined alarm setpoint.
Low Temperature
Air temperature is below user-defined alarm setpoint.
High Humidity
Humidity is above user-defined alarm setpoint.
Low Humidity
Humidity is below user-defined alarm setpoint.
Sensor Failure
Sensor is disconnected or faulty. (The failed sensor is identified.)
Communication Failure
External and/or internal communication lost (BMS or pLAN).
Condensate Pan
Full. Water level in condensate pan is reaching an unsafe level.
Moisture
Water sensed by any combination of a leak detector or condensate pan level switch.
Fan Failure
Upper, middle, and/or lower fan failure.
Change Filter
Filter replacement time interval elapsed; filter needs to be replaced.
No Airflow
Insufficient airflow per air-proving switch.
Smoke/Fire
An alarm condition detected by the smoke detector or firestat.
Optional Temp High Alarm
Temperature is above alarm threshold (user configurable).
Optional Temp Low Alarm
Temperature is below alarm threshold (user configurable).
High Head Pressure
Head pressure is above user-configured alarm threshold.
Low Suction Pressure
Suction pressure is below user-configured alarm threshold.
EVD Driver Offline
EEV and EHGB control driver error.