Chapter 4: E2 Controller
Table 4-10. Factory default setpoints.
Parameter
Default  Value
Temperature Setpoint
72° F
Compressor Cut- in
74° F
Compressor Cut- out
72.3° F
Minimum Fan Speed
40%
Maximum Fan Speed
100%
Dehumidification Fan Speed
60%
Humidity Setpoint
45% RH
Dehumidify Cut-in
50% RH
Dehumidify Cut-out
47% RH
Figure 4-63. Set Passwords screen.
The second Service>Save Cfg menu screen allows you to set new passwords for entering the Control and Service menus.
4.5.5.10 Factory Menu
Figure 4-64. Factory Menu screen.
The Factory Menu loop may be accessed from the Service>Factory screen. You must enter the factory-level password to gain 
access to the loop. Contact Black Box Tech Support for the password and for guidance when adjustments must be made at this 
level.