Chapter 4: E2 Controller
A workgroup should ALWAYS start with controller address 1 and go up from there. DO NOT skip over controller addresses. The 
list of suitable controller/display terminal address pairs is shown below:
Table 4-11. Corresponding Controller to Terminal pLAN Addresses.
Controller (I/O board)
1
2
3
4
5
6
7
8
Display Terminal
32
31
30
29
28
27
26
25
You must assign the terminal and controller I/O board addresses for each controller to be grouped. Review Sections 4.6.2.1 to 
4.6.2.3 first, before turning power on and assigning addresses. Do not interconnect the controllers together before assigning their 
terminal and I/O board pLAN addresses.
The first step is to change the terminal address of each controller to 0, referring to Section 4.6.2.1 below. You must set the  
terminal address to 0 before you can assign the controller (I/O board) address.
NOTE:  If the terminal remains inactive (no key is pressed) for more than 30 seconds, the group setup procedure is exited  
automatically, without saving any changes.
4.6.2.1 Configure the Terminal Address
The address of the terminal (display) can only be configured if its telephone jack is connected to the I/O control module in the 
electric box and power is turned on. The factory default value for the display terminal address is 32. To reassign the terminal 
address, press and hold the (up-arrow ( 
), down-arrow ( 
) and Enter (
) keys simultaneously for five seconds until the 
Address Configuration screen shown below appears with the flashing cursor in the top left corner:
Figure 4-68. Terminal (Display) Address screen.
1.  To change the address of the terminal (Display address setting), press the Enter 
 key once. The cursor will move to the 
address field (nn).
2. Use the up   and down   arrow keys to select the desired value (0), and confirm by pressing Enter 
 again.
Figure 4-69. Display Address screen.
The Display Address Changed screen will appear, indicating the display address selected is not the same as the one saved  
previously and the new value will be saved to the permanent memory.
3. Once the terminal address is set to zero, cycle the power to the unit Off and then back On.
NOTE:  If the “Display address setting:__" field is set to 0, the terminal will communicate with the controller (I/O board) using 
point-to-point protocol (not pLAN). The display field “I/O Board address:__” will disappear as it has no meaning until you 
set the controller (I/O board) pLAN address.