Black Box CRDX-A-FS-12KW Manuale Utente

Pagina di 132
724-746-5500   |   blackbox.com 
724-746-5500   |   blackbox.com 
Page 97
Chapter 4: E2 Controller
Factory>Group>Group Status (Screen 8) provides an overview of the current duty status for all the A/C units combined in the 
group.
Table 4-23. Factory>Group>Group Status (Screen 8) parameters.
Display Description
Description
Variables
Default
Running
Display indicates how many units in the group are currently operating.
0 to 8
0
Active
Display indicates how many units in the group are currently active.
0 to 8
0
Standby
Display indicates how many units in the group are currently in standby. 
0 to 8
0
Assist
Display indicates how many units in the group are currently operating in the capacity assist mode.
0 to 8
0
Online
Display indicates how many units in the group are currently available to operate.
0 to 8
0
Out of Service
Display indicates how many units in the group are not available to operate. 
The final step to configure a workgroup is to access the Service>Options>Group Setup screens used to configure parameters that 
apply to how individual A/C units interact in the workgroup (see Section 4.6.2.7).
Figure 4-84. Factory>Group>Plan timing (Screen 9).
Table 4-24. Factory>Group>Plan timing (Screen 9) parameters.
Display Description
Description
Variables
Default
Lead unit
Display indicates which unit is currently the lead.
0 to 8
0
Plan timer
Display indicates the time delay (in seconds) between the detection of 
a communication failure and the annunciation of a Comm alarm.
0 to 60
30
pLAN present
Display indicates if a pLAN is detected by the controller.
0 = No
1 = Yes
No
4.6.2.7 Service>Options>Group Menu Screens
Accessed in the Service menu, the Service>Options>Group Setup screens only appear if two or more units are wired together as 
a workgroup.
Group Setup
Figure 4-85. Group setup screen.