American Power Conversion Smart-UPS VT Manuale Utente

Pagina di 56
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 
17
Display Messages/Troubleshooting
This section lists the status and alarm messages that the UPS might display. The messages are listed 
in alphabetical order, and a suggested corrective action is listed with each alarm message to help you 
troubleshoot problems. 
Display messages
Display message
Meaning
Corrective action
Automatic Self Test 
Started.
The UPS has started pre-programmed 
battery test.
No corrective action necessary.
Batt Temperature 
Exceeded Upper Limit.
The temperature of one or more bat-
tery units has exceeded system 
specifications.
Contact APC Customer Support. 
See rear cover.
Battery over-voltage 
warning.
The battery voltage is too high and 
the charger has been deactivated.
Contact APC Customer Support. 
See rear cover.
Bypass Not Available 
Input Freq/Volt Out Of 
Range.
The frequency or voltage is out of 
acceptable range for bypass. This 
message occurs when the UPS is 
online, and indicates that the bypass 
mode may not be available if 
required.
Correct the input voltage to provide 
acceptable voltage or frequency.
Discharged Battery.
The UPS is in battery operation and 
the battery charge is low. 
Note: Runtime is limited in duration. 
No corrective action necessary. Shut 
down the system and the load 
equipment or restore incoming 
voltage.
Emergency PSU Fault.
Redundant Emergency Power Supply 
Unit (PSU) is not working. The UPS 
will continue to work normally, but 
the PSU should be replaced.
Contact APC Customer Support. See 
rear cover.
EPO Activated.
Emergency Power Off Switch has 
been activated.
Deactivate Emergency Power Off 
Switch. 
Fan fault.
A fan has failed.
Contact APC Customer Support. See 
rear cover.
Int. Mech. Bypass 
Switch Closed.
The internal mechanical switchgear is 
closed.
No corrective action necessary. The 
UPS is in internal mechanical bypass 
operation.
Int. Mech. Bypass 
Switch Open.
The internal mechanical switchgear is 
open.
No corrective action necessary.
Low-Battery.
The UPS is in battery operation and 
the battery charge is low.
Note: Runtime is limited in duration.
Shut down the system and the load 
equipment or restore incoming volt-
age.