External Connection - 10kVA 400V UPS
990-2440
AIS 5000 400V Installation Manual
25
Frequency Regulation
50 Hz, + 0.1% free running
Output Voltage Range
100% static symmetrical load + 1%, 100% static asymmetrical load 
+ 3%, no load to full load + 4%
Output Harmonic Distortion
<3% linear load <5%
Load Crest Factor
5: 1
Load Power Factor
0.9 leading to 0.7 lagging
Overload Capacity
150% for 1 min., 125% for 10 min., Bypass Operation 1000% for 5 
cycles
Connection Type
3 PH + N + G
Battery - External Only
Nominal Voltage 
(Nominal battery voltage assumed to be 2.0 V/cell 
(lead technology)
240 V
Number of Battery Cells
120
Float Charge Voltage
272 Volt DC programmable
Charge Voltage Range
100 to 115% of the DC nominal Voltage, + 1% IU characteristic
Low Battery Warning Range
210-222 Vdc (Factory Setting 210 V)
Low Battery Shutdown
204 Vdc
Full Load (P) 
(The battery power takes in to account the DC-AC 
efficiency of the main inverter for linear load)
9.2 kW
Recommended Breaker Size [A]
60 A
Connection Type
Hard Wire 3-wire (DC+/- + G)
Nominal Discharge Current [A] 
(The battery nominal discharge current is based on 
the nominal cell Voltage of 2.0 V/cell - number 
of cells = 120 which gives a total Voltage of 240V)
38 A
Max. Discharge Current [A] 
(The battery max. discharge current is based on a cell 
end Voltage of 1.70V/cell which gives a total Voltage 
of 204V)
46 A
Communication and Management
Control Panel
Multi-function LCD status and control console 
RS232 Port
Yes
Network Management Card 10/100 
Base T
Yes
Audible Alarm
Audible and visible alarms prioritized by severity
Slots Empty
1
Modbus/BMS Card
Optional
Electrical Output