56      Chapter 7  “1+N” System 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
7.4.3   Power Cables 
The wiring of power cables is similar to that of single module system. Refer to 3.1  Power Cabling
The bypass and the main input sources must be referenced to the same neutral potential and input earth leakage 
monitoring devices, if installed, must be located upstream of the common neutral sinking point. 
7.4.4   Control Cables 
Control cable connection of dual bus system consisting of two single units 
If the dual bus system consists of two single units, use the optional 9-core LBS cable to connect between the LBS 
interfaces (X4 socket on parallel board) of the two single units, and use another optional LBS cable to connect 
between any two 25-core interfaces (X2-1 or X2-2) of the two single units, as shown in Figure 7-4. 
 Warning 
Although the dedicated 25-core LBS cable looks like the parallel cable, it is absolutely not the parallel cable, and cannot be 
replaced by it. Otherwise, UPS system chaos may occur.   
 
Parallel board
X4
04116319  20m  DB9-DB9
04115338  10m  DB9-DB9
04115339  15m  DB9-DB9
04116100  15m  DB25-DB25
Parallel board
UPS unit 1
UPS unit 2
LBS cable
LBS cable
X4
X2-1
X2-2
X1-2
X1-1
X2-1
X2-2
X1-2
X1-1
 
Figure 7-4    Control cable connection of dual bus system consisting of two single units 
Control cable connection of dual bus system consisting of a single unit and a parallel system 
Figure 7-5 shows the control cable connection of the dual bus system consisting of a single unit and a parallel system 
composed of two or more single units. Use the optional 9-core LBS cable to connect from the LBS interface (X4 
socket on parallel board) of the single unit to the LBS interface of any single unit in the parallel system; and use 
another optional LBS cable to connect from any 25-core interface (X2-1 or X2-2) of the single unit to the LBS 
interface of any single unit except for the aforesaid one in the parallel system, note that this LBS cable has a 9-core 
end and a 25-core end, respectively connecting the X4 interface of the parallel system and the 25-core interface of 
the single unit.