Emerson Remote Monitoring Panel Manuale Utente

Pagina di 28
Operation
18
Bypass Phase Reversed
The phase sequence direction of bypass voltage is reversed.
Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C 
lags 120 degrees behind phase B.
Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it 
if it is found to be in error
Load Impact Transfer
A transfer to bypass occurred due to a large step load. The UPS should recover automatically. 
Turn on connected equipment in sequential order to reduce the step loading of the inverter.
Transfer Time-out
The load is on bypass power due to excessive number of transfers that occurred within the last 
hour.
The UPS will recover automatically and will transfer the load back to inverter power within an 
hour.
Load Sharing Fault
UPS modules within a parallel system are not sharing the load current equally.
DC Bus Abnormal
DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass.
System Transfer
The whole paralleled UPS system transferred to bypass at the same time. This message will 
appear on the UPS which passive transfer to bypass 
Parallel Board Fault
Malfunction of the paralleling control circuits of this UPS module. Can cause “System Transfer” 
to bypass.
DC Bus Over Voltage
Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high. 
Check whether there is a fault in rectifier side. If no, then check whether overload occurs. 
Restart the inverter after resetting the fault
Parallel Connect Fault
The parallel cables are not connected correctly in a parallel system.
Reset the fault by pressing the “fault clear” button, then restart the inverter by pressing the 
“inverter on” button.
Bypass Over Current
Bypass current is over limit above 135% rating. The UPS just alarms and does nothing.
LBS Active
Load Bus Synchronization is active. The UPS is acting as an LBS master or slave in a dual bus 
configuration.
Setting Save Error
History records not saved. (Reserved)
Mains Neutral Lost
AC Input mains reference neutral not detected.
Protocol version clash
Firmware incompatibility between Monitor Board and Digital Signal Processor Board.
Battery ground fault
Battery leakage to ground detected (option)
Inv. Turned On Manually
Manual Turn On via front panel
Inv. Turned Off Manually
Manual Turn Off via front panel
EPO
Emergency Power Off direct access key pressed or external command received
Transfer Confirm
Prompt to press “enter” key to acknowledge that an interrupted load transfer to bypass will 
happen.
Transfer Cancel
Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will happen.
Unit Off Confirm
Prompt to press “enter” key to acknowledge that the UPS will be disconnected from other 
paralleled UPS modules.
System Off Confirm
Prompt to press “enter” key to acknowledge that the all paralleled UPS will be disconnected 
from the load.
Fault Reset
Fault clear direct access key pressed
Alarm Silence
Silence On/Off direct access key pressed
Turn On Fail
Inverter failed to turn on when Inverter On direct access key was pressed. This may be as a 
result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready.
Alarm Reset
Fault clear or Silence On/Off direct access key pressed
Bypass Mode
Load supplied from AC input bypass supply.
Normal Mode
Load supplied from Inverter output through double conversion of the AC mains input supply.
Battery Mode
Load supplied from Inverter output through double conversion of the Battery supply.
Source share mode
Load supplied from Inverter output through shared double conversion of the AC mains input 
supply and of the Battery supply.
Table 13
RMP messages (continued)
Message
Description / Suggested Action (if any)