Modbus 485 and Modbus IP Protocols - Thermal Management Products
39
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 11
Liebert CRV
 - Status and Coil
Controller
Liebert iCOM
®
 v4
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
Supply Air Over Temperature
10001
1
Active on Alarm
Supply Air Under Temperature
10002
1
Active on Alarm
Return Air Over Temperature
10003
1
Active on Alarm
Supply Air Sensor Issue
10004
1
Active on Alarm
High Return Humidity
10005
1
Active on Alarm
Low Return Humidity
10006
1
Active on Alarm
Humidifier Hours Exceeded
10007
1
Active on Alarm
Dehumidifier Hours Exceeded
10008
1
Active on Alarm
Humidifier Under Current
10009
1
Active on Alarm
Humidifier Over Current
10010
1
Active on Alarm
Humidifier Low Water
10011
1
Active on Alarm
Humidifier Cylinder Worn
10012
1
Active on Alarm
Humidifier Issue
10013
1
Active on Alarm
Ext Humidifier Lockout
10014
1
Active on Alarm
Humidifier Control Board Not Detected
10015
1
Active on Alarm
Return Humidity Out Of Proportional Band
10016
1
Active on Alarm
Loss of Air Flow
10017
1
Active on Alarm
Fan Hours Exceeded
10018
1
Active on Alarm
Top Fan Issue
10019
1
Active on Alarm
Bottom Fan Issue
10020
1
Active on Alarm
Remote Sensor Issue Module Index 1
10021
1
Active on Alarm
Remote Sensor Issue Module Index 2
10022
1
Active on Alarm
Remote Sensor Issue Module Index 3
10023
1
Active on Alarm
Remote Sensor Issue Module Index 4
10024
1
Active on Alarm
Remote Sensor Issue Module Index 5
10025
1
Active on Alarm
Remote Sensor Issue Module Index 6
10026
1
Active on Alarm
Remote Sensor Issue Module Index 7
10027
1
Active on Alarm
Remote Sensor Issue Module Index 8
10028
1
Active on Alarm
Remote Sensor Issue Module Index 9
10029
1
Active on Alarm
Remote Sensor Issue Module Index 10
10030
1
Active on Alarm
Compressor 1 High Head Pressure
10031
1
Active on Alarm
Compressor 1 Low Suction Pressure
10032
1
Active on Alarm
Compressor 1 Hours Exceeded
10033
1
Active on Alarm
Dig Scroll Comp 1 Temp Sensor Issue
10034
1
Active on Alarm
Dig Scroll Comp 1 Over Temp
10035
1
Active on Alarm
Compressor 1 Low Pressure Transducer Issue
10036
1
Active on Alarm
Ext Compressor Lockout
10037
1
Active on Alarm
Compressor 1 Short Cycle
10038
1
Active on Alarm
Compressor 1 High Pressure Transducer Issue
10039
1
Active on Alarm
Compressor 1 Pump Down Issue
10040
1
Active on Alarm
Reheater Over Temperature
10041
1
Active on Alarm
Electric Reheater 1 Hours Exceeded
10042
1
Active on Alarm
Ext Reheat Lockout
10043
1
Active on Alarm
Condenser 1 Issue
10044
1
Active on Alarm
Condenser VFD Issue
10045
1
Active on Alarm
Condenser TVSS Issue
10046
1
Active on Alarm