Emerson GXT3 230V Manuale Utente

Pagina di 44
Troubleshooting
31
11.1.2 Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS 
operating status. The audible alarm will sound as described in Table 5.
Table 5
Audible alarm description
Condition
Alarm
Battery discharge
Half-second beep every 10 seconds
Low battery
Two half-second beeps every 5 seconds
UPS fault, load on bypass
1-second beep every 4 seconds
UPS fault, no power to load
Continuous
Overload
Half-second beep every half second
Battery replacement
2-second beep every 60 seconds
Battery loss
Continuous
Wiring problem
(loss of proper grounding for UPS)
Continuous
Bypass reminder
1-second beep every 2 minutes