Specifications
34
12.0 S
PECIFICATIONS
Table 7
UPS specifications
Model #
Liebert
®
 GXT3
 5000RT230U
Rating
5000VA/4000W
Dimensions, mm (in)
Unit, W x D x H
570 x 430 x 220 (22.4 x 16.9 x 8.7)
Shipping, W x D x H
745 x 530 x 516 (29.3 x 20.9 x 20.3)
Weight, kg (lb)
Unit
60 (132.2)
Shipping
71 (156.5)
Input AC Parameters
Operating Frequency, Nom
50 or 60Hz (Factory Default = 50)
Factory Default VAC
 230VAC 
User-Configurable VAC
220/230/240VAC
(May be modified using included configuration program)
Operating Voltage Range Without Battery Operation
176 - 280VAC
Maximum Allowable VAC
280VAC
Input Frequency Without Battery Operation
40 - 70Hz
Input Power Connection
Hardwire Terminal Block Standard
Output AC Parameters
Factory Default VAC
 
230VAC 
Output Connections
Hardwire Terminal Block Standard
Frequency
50Hz or 60Hz, Nominal
Waveform
Sinewave
Main Mode Overload >200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 
seconds; 105 - 130% 1 minute
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid 
Quantity x V
20 x 12V
Battery Mfr. / Part #
5AH battery, CSB HR1221W or YUASA NPH5-12
Recharge Time (Internal Batteries)
3 hr. to 90% capacity after full discharge into 100% load
Bypass Protection Limits 
Disable Bypass Operation
If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation
If input voltage returns to within ±10% of nominal output 
voltage
Disable Bypass operation
When the input frequency prevents synchronous operation
Environmental
Operating Temperature, °C (°F)
Storage Temperature, °C (°F)
-15 to 50 (5 to 122)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise
 <55 dBA at 1 meter from the rear;
<50 dBA, at 1 meter from the front or sides