Emerson 721NPBB Manuale Utente

Pagina di 72
UM582127000 
User Instructions 
Issue AC, January 2, 2013 
Spec. No. 582127000 (Model 721
NPBB
 
Page 48 
Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Optional LVD Driver and LVD Driver Lite Circuit Card Replacement 
Procedure 
1)  Performing this procedure may activate external alarms.  Do one of the following.  
If possible, disable these alarms.  If these alarms cannot be easily disabled, 
notify the appropriate personnel to disregard any future alarms associated with 
this system while the procedure is being performed. 
Danger:  Performing the next steps exposes service personnel to battery 
potential.  Exercise extreme caution not to inadvertently contact or 
have any tool inadvertently contact any energized electrical 
termination. 
2)  Open the distribution cabinet
’s front door by turning the latch in the 
counterclockwise position. 
Warning:  Damage to the circuit card may result if the next step is not followed. 
3)  Connect an approved grounding strap to your wrist.  Attach the other end to a 
suitable ground. 
4)  If any of the low voltage disconnect contactors is open and it is desired to be 
closed, push the LVD Inhibit Switch located on the circuit card installed in the 
main bay to the UP position momentarily and then leave the switch in the middle 
(OFF) position. 
5)  Remove the top and front panels to access the circuit cards at the bottom of the 
distribution cabinet. 
6)  Carefully label the connectors plugged into the circuit card.  These connectors 
must be plugged into the same connectors on the replacement circuit card.  
Refer to Figure 4-14 or Figure 4-15. 
7)  Unplug all connectors plugged into the circuit card. 
8)  Remove the screws securing the circuit card and remove the circuit card from the 
distribution cabinet. 
9)  Slide the replacement circuit card into the mounting position inside the 
distribution cabinet, and secure with the screws removed from the old circuit 
card. 
10) Ensure that the LVD Inhibit Switch is in the middle (OFF) position. 
11) Plug all connectors removed from the old circuit card into the same position on 
the replacement circuit card. 
12) Push the LVD Inhibit Switch to the down (ON) position. 
13) Remove the grounding wrist strap. 
14) Reinstall the top and front panels that cover the circuit cards at the bottom of the 
distribution cabinet. 
15) Close the distribution cabinet
’s front door.  Turn the latch clockwise to secure the 
door. 
16) Enable the external alarms, or notify appropriate personnel that this procedure is 
finished. 
17) Ensure that there are no local or remote alarms active on the system.