Emerson 30-130KVA Dépliant

Pagina di 2
L
IEBERT
 N
POWER
™ 3-P
HASE
 UPS: 30-130
K
VA, 60 H
Z
, 208 
OR
 480VAC
General Specifications
INPUT
Voltage
208 or 480VAC, 60 Hz
3-phase, 3- or 4-wire plus ground
Voltage Range
+10, -15% 
(no battery discharge at -20%)
Frequency Range
60 Hz, ±5
Current Distortion
10% maximum reflected THD at full load with 
optional input filter; 30% THD without filter
Current Limit
115% of full load input current
Current Walk-in
20 seconds to full load
Power Factor
0.80 lagging minimum at full load; up to 0.96 
lagging at full load with optional input filter
Surge Protection
Sustains input surges without damage, per
criteria listed in ANSI C62.41-1980 (IEEE 587)
ENVIRONMENTAL
Operating 
Temperature
UPS: 32° to 104°F (0-40°C)
Battery: 68° to 86°F (20-30°C)
Non-Operating Temp. -4° to 158°F (-20° to 70°C)
Relative Humidity
0-95% non-condensing
Operating Altitude
Up to 6600 ft. (2000m) without derating
Acoustical Noise
Less than 65 dBA typical, measured 
3.3 ft. (1m) from the unit
OUTPUT
Voltage
208 or 480VAC
3-phase, 4-wire plus ground
Voltage Adjustment 
Range
±5%
Voltage Regulation
±0.5% for balanced load
±1.0% for 100% unbalanced load
Dynamic Regulation ±5% deviation for 100% load step
±1% for loss or return of AC input
Transient Response 
Time
Recover to ±1% of steady state within 1 cycle
Voltage Distortion
For linear loads, 1% THD; less than 2.5% THD
for 100% nonlinear loads w/o kVA/kW derating
Phasing Balance
120° ±0.5° for balanced load. 
120° ±1° for 100% unbalanced load
Frequency
Regulation
±0.1%
Load Power
Factor Range
1.0 to 0.7 lagging without derating
Overload
125% of full load for 10 minutes
150% for 1 minute w/ true sinusoidal waveform
STANDARDS
ETL listed to UL 1778 UPS standards and CSA certified. Meets current 
requirements for safe high performance UPS operation.
Liebert has re-
invented the 
double-conversion 
UPS. The Npower is 
the result of an 
international design 
collaboration and 
more than a decade 
of advanced 
research.
Every aspect of the 
Npower shows 
careful design and 
attention to detail. The rugged 
powertrain and advanced 
ActiveStar™ controls were 
subjected to computer simulations 
and thermal analysis to ensure 
reliable performance in every 
environment.
Even the physical packaging is 
uniquely efficient, to make fully 
configured systems more compact 
than other products on the market.
Best of all, it’s a Liebert product—
designed to give the same million-
hour critical bus MTBF as its older 
brothers.
• Unmatched heritage of 
reliability and availability
• Smallest system footprint
• Excellent efficiency with non-
linear loads and partial loads
• Outstanding dynamic response
• All-digital ActiveStar™ controls 
and graphical user interface
Npower Matching Battery Cabinet
Model
Run Time (minutes) for kVA:
Dimensions
Weight
30 40 50 65 80 100 130 WxDxH, in. (mm)
lb. (kg)
1FJ
12
7
-
-
-
-
-
25x32.5x71
(635x825x1800)
1,600 (725)
1HJ
21 14 10
7
5
-
-
1,800 (815)
1LJ
28 20 14
8
5
-
-
2,350 (1,065)
1MJ
36 25 18 12
8
5
-
2,350 (1,065)
1PJ
53 38 28 20 15 10
-
3,000 (1,360)
1PJ(130)
-
-
-
-
-
-
7
49x32.5x71
(1250x825x1800)
3,350 (1,520)
1RJ
62 45 34 25 19 13
9
3,700 (1,680)
1UJ
72 52 39 30 23 17 12
4,000  (1,815)
1WJ
104 74 55 40 33 25 16
5,050 (2,290)
2PJ
126 83 67 50 38 28
-
(2) 25x32.5x71
635x825x1800)
6,000 (2,720)
2PJ(130)
-
-
-
-
-
-
20
(2) 49x32.5x71
(1250x825x1800)
6,700 (3,040)
2RJ
144 104 76 55 45 35 25
7,400 (3,360)
2UJ
156 111 90 67 52 40 30
8,000 (3,630)
2WJ
-
-
-
97 74 55 40
10,100 (4,580)
3PJ
204 145 108 78 63 48
-
(3) 25x32.5x71
635x825x1800)
9,000 (4,080)
3PJ(130)
-
-
-
-
-
-
35
(3) 49x32.5x71
(1250x825x1800)
10,050 (4,560)
3RJ
223 161 129 94 72 54 39
11,100 (5,040)
3UJ
265 187 142 105 81 65 48
12,000 (5,445)
3WJ
421 302 217 157 124 94 69
15,150 (6,870)
4PJ
301 206 154 111 90 68
-
(4) 25x32.5x71
(635x825x1800)
12,000 (5,440)
4PJ(130)
-
-
-
-
-
-
50
(4) 49x32.5x71
1250x825x1800
13,400 (6,080)
4RJ
329 224 182 134 102 77 55
14,800 (6,720)
4UJ
377 266 201 147 111 91 67
16,000 (7,260)
4WJ
480 423 320 222 180 135 97
20,200 (9,160)
Maintenance Bypass Cabinets
Model
Dimensions
Weight, lb. (kg) for kVA:
WxDxH, in. (mm)
30-50
65-80
100-130
L or N
25x32.5x71
(635x825x1800)
660 (299)
750 (340)
800 (363)
P or Q
31.7x32.5x71
(805x825x1800)
1,210 (549)
1,320 (599)
1,540 (699)
Slim-Line Distribution Cabinet
kVA
Dimensions
Weight
WxDxH, in. (mm)
lb. (kg)
All
10x32.5x71
(254x825x1800)
250 (113)